Rockwell Automation 20D PowerFlex 700H and 700S Frame 9...14 Drives User Manual
Page 180

180
Rockwell Automation Publication PFLEX-IN006E-EN-P - July 2013
Appendix A
Specifications
Table 13 - 540 Volt DC Input Frames 9…14 Drive Protection Devices
20xF1K0
13
1000
–
1038
1300 (1 per phs)
650 (2 per phs)
2300
1300 (1 per phs)
650 (2 per phs)
3000
170M6466
(5)
3000
1300
–
900
927
1200 (1 per phs)
600 (2 per phs)
2000
1200 (1 per phs)
600 (2 per phs)
2700
170M6466
(5)
2700
1200
20xF1K1
13
1100
–
1189
1500 (1 per phs)
750 (2 per phs)
2600
1500 (1 per phs)
750 (2 per phs)
3500
170M6466
(5)
3500
1500
–
1000
1038
1300 (1 per phs)
650 (2 per phs)
2300
1300 (1 per phs)
650 (2 per phs)
3000
170M6466
(5)
3000
1300
20xF1K5
14
1500
–
1511
1900 (1 per phs)
650 (3 per phs)
3300
1900 (1 per phs)
650 (3 per phs)
4500
170M6466
4500
1900
–
1300
1310
1700 (1 per phs)
575 (3 per phs)
2900
1700 (1 per phs)
575 (3 per phs)
3900
170M6466
3900
1700
20xF1K9
(2)
14
1800
–
1914
2400 (1 per phs)
800 (3 per phs)
4200
2400 (1 per phs)
800 (3 per phs)
5700
170M6466
5700
2400
–
1500
1511
1900 (1 per phs)
650 (3 per phs)
3200
1900 (1 per phs)
650 (3 per phs)
4500
170M6466
4500
1900
20xF2K2
(2)
14
2000
–
2267
2900 (1 per phs)
950 (3 per phs)
5000
2900 (1 per phs)
950 (3 per phs)
6700
170M6466
6700
2900
–
1800
1914
2400 (1 per phs)
800 (3 per phs)
4200
2400 (1 per phs)
800 (3 per phs)
5700
170M6466
5700
2400
(1) 20DF820 drives (ND) are only capable of producing 95% of starting torque under 10 Hz.
(2) Not available with 700S Control.
(3) Minimum protection device size is the lowest rated device that supplies maximum protection without nuisance tripping.
(4) Maximum protection device size is the highest rated device that supplies drive protection.
(5) These fuses and disconnect are supplied with AC input NEMA/UL Type 1 drives.
(6) Inverse time breaker. Ratings shown are maximum.
(7) Maximum allowable rating by US NEC. Exact size must be chosen for each installation.
(8) Motor Circuit Protector - instantaneous trip circuit breaker. For US NEC minimum size is 125% of motor/drive FLA. Ratings shown are suggested. Instantaneous trip settings must be set to US NEC code. Not
to exceed 1300% FLA.
Drive Catalog
Number
Fram
e
kW Rating
Input
Ratings
Dual Element Time Delay Fuse
Non-Time Delay Fuse
Bussmann Style Semi-
Conductor Fuse
Circuit
Breaker
(6)
Motor Circuit
Protector
(8)
ND
HD
Amps
Min.
(3)
Max.
(4)
Min.
(3)
Max.
(4)
Max.
(7)
Max.
Drive Catalog Number Frame kW Rating
DC Input Ratings Fuse
Bussmann Style Fuse
ND
HD
Amps
20xH261
9
132
-
307
500
170M6608
-
110
241
500
170M6608
20xH300
9
160
-
353
630
170M6610
-
132
288
630
170M6610
20xH385
10
200
-
453
700
170M6611
-
160
353
700
170M6611
20xH460
10
250
-
541
900
170M6613
-
200
453
900
170M6613
20xH500
10
250
-
589
500 (2 per phs)
170M6608
-
250
494
500 (2 per phs)
170M6608
20xH590
11
315
-
695
550 (2 per phs)
170M6609
-
250
612
550 (2 per phs)
170M6609
20xH650
11
355
-
765
630 (2 per phs)
170M6610
-
315
695
630 (2 per phs)
170M6610
20xH730
11
400
-
859
700 (2 per phs)
170M6611
-
355
765
700 (2 per phs)
170M6611
20xH820
12
450
-
965
700 (2 per phs)
170M6611
-
400
859
700 (2 per phs)
170M6611
20xH920
12
500
-
1083
550 (3 per phs)
170M6609
-
450
965
550 (3 per phs)
170M6609
20xH1K0
12
560
-
1213
630 (3 per phs)
170M6610
-
500
1083
630 (3 per phs)
170M6610
20xH1K1
13
630
-
1354
2400
170M7107
-
560
1213
2400
170M7107
20xH1K3
13
710
-
1530
2400
170M7107
-
630
1354
2400
170M7107