Rockwell Automation 20D PowerFlex 700H and 700S Frame 9...14 Drives User Manual
Page 141

Rockwell Automation Publication PFLEX-IN006E-EN-P - July 2013
141
Frame 14 Mechanical Installation
Chapter 10
Ungrounded, High Resistive
Ground or Grounded B Phase
Delta Installations
Frame 14 size drives are equipped with common mode capacitors. To guard
against drive damage, these capacitors should be disconnected depending upon
the type of ground system on which the drive is installed.
To access and move the common mode jumper(s) and disconnect the capacitor
connections you must first move the control frame and remove the protective
covers from the converter unit. These steps are detailed on the following pages.
Note: See Wiring and Grounding Guidelines for Pulse Width Modulated
(PWM) AC Drives - Installation Instructions, publication
, for
additional information on an ungrounded distribution system or high resistive
ground installation.
Figure 60 - Common Mode Jumper and Rectifier Circuit Board Location
Converter
Unit
Common
Mode
Jumper
Control Frame not shown for clarity only
Inverter Unit
Inverter Unit
1500A Drives
Drives Above 1500A
Inverter Unit
Converter
Unit
Inverter Unit
Converter
Unit
There is one jumper for
each rectifying module.
The rectifying modules
and jumpers are located
on the left side of the
power stack on the
drive’s converter units.
Rectifier
board
Rectifier