Dc- dc – Rockwell Automation 20D PowerFlex 700H and 700S Frame 9...14 Drives User Manual
Page 117
Rockwell Automation Publication PFLEX-IN006E-EN-P - July 2013
117
Frame 12 Mechanical Installation
Chapter 8
Table 26 - Power Terminal Specifications
Figure 47 - Power Terminal Locations
No. Name
Description
Wire Size Range
(1)(2)
Torque
Terminal Bolt Size
(3)(4)
Maximum
Minimum
Recommended
1
Input Power Terminal Block
(3)
1L1, 1L2, 1L3, 2L1, 2L2, 2L3
Input power
300 mm
2
(600 MCM)
2.1 mm
2
(14 AWG)
40 N
•
m
(354 lb
•
in)
M12
2
Output Power Terminal Block
((3)
1U/1T1, 1V/1T2, 1W/1T3,
2U/2T1, 2V/2T2, 2W/2T3
Motor connections
300 mm
2
(600 MCM)
2.1 mm
2
(14 AWG)
40 N
•
m
(354 lb
•
in)
M12
3
SHLD Terminal, PE, Motor Ground
(3)
Terminating point for wiring shields
300 mm
2
(600 MCM)
2.1 mm
2
(14 AWG)
40 N
•
m
(354 lb
•
in)
M10
4
DC Bus
(3)
(2 Terminals; DC–, DC+)
DC input or external brake
300 mm
2
(600 MCM)
2.1 mm
2
(14 AWG)
40 N
•
m
(354 lb
•
in)
M12
5
Cable Clamp for Shield
(1) Maximum/minimum sizes that the terminal block will accept - these are not recommendations.
(2) Do Not exceed maximum wire size. Parallel connections may be required.
(3) These connections are bus bar type terminations and require the use of lug type connectors.
(4) Apply counter torque to the nut on the other side of terminations when tightening or loosening the terminal bolt in order to avoid damage to the terminal.
DANGER
DANGER
DC BUS CONDUCTORS AND CAPACITORS
OPERATE AT HIGH VOLTAGE. REMOVE POWER
AND WAIT 5 MINUTES BEFORE SERVICING
DANGER
DANGER
DC BUS CONDUCTORS AND CAPACITORS
OPERATE AT HIGH VOLTAGE. REMOVE POWER
AND WAIT 5 MINUTES BEFORE SERVICING
Cat No.
1234567890-*
FIELD INSTALLED OPTIONS:
FIELD INSTALLED OPTIONS:
DC- DC+
DC- DC+
1L1
1L2
1L3
2L1
2L2
2L3
1U/T1
1V/T2
1W/T3
2U/T1
2V/T2
2W/T3
Enclosure Style A Shown
1
1
5
5
3
2
2
4
4