Frame 9 Mechanical Installation
Chapter 5
Power Wiring
Table 22 - Power Terminal Specifications
Figure 16 - Terminal Locations and Power Terminal Block
No.
Name
Description
Wire Size Range
(1)
Torque
Maximum
Minimum
Recommended
1
Input Power Terminal Block
(2)
L1, L2, L3
Input power
185.0 mm
2
(350 MCM)
95.0 mm
2
(4/0 AWG)
40 N
•
m
(354 lb
•
in)
2
Output Power Terminal Block
(2)
U/T1, V/T2, W/T3
Motor connections
185.0 mm
2
(350 MCM)
95.0 mm
2
(4/0 AWG)
40 N
•
m
(354 lb
•
in)
3
SHLD Terminal, PE, Motor Ground
Terminating point for wiring shields
95.0 mm
2
(4/0 AWG)
5.0 mm2
(10 AWG)
22 N
•
m
(195 lb
•
in)
4
DC Bus
(3)
(2 Terminals; DC–, DC+)
DC input or external brake resistor
(Internal Brake option not provided - See Frame 9 DC Bus/
Brake Connections on page
185.0 mm
2
(350 MCM)
95.0 mm
2
(4/0 AWG)
40 N
•
m
(354 lb
•
in)
DC Bus w/Brake
(3)
(3 Terminals; DC–, DC+/R+, R–)
DC input/internal brake
Internal Brake option not provided - See Frame 9 DC Bus/
Brake Connections on page
185.0 mm
2
(350 MCM)
95.0 mm
2
(4/0 AWG)
40 N
•
m
(354 lb
•
in)
5
Cable Clamp for Shield
(1) Maximum/minimum sizes that the terminal block will accept - these are not recommendations.
(2) Do Not exceed maximum wire size. Parallel connections may be required.
(3) DC terminal and brake lugs can be removed.
DC
–
DC+/R+
R–
DC –
DC+/R+
R–
L1
AC Line Input Power
To Motor Leads
L2
L3
L1
L2
L3
U/T1 V/T2 W/T3 U/T1 V/T2 W/T3
DC-, DC+/R+, R- terminals
shown with protective cover
removed.
1
2
3
4