Minimum mounting clearances, Operating temperatures, Nameplate location – Rockwell Automation 20D PowerFlex 700H and 700S Frame 9...14 Drives User Manual
Page 64: Minimum mounting clearances operating temperatures
64
Rockwell Automation Publication PFLEX-IN006E-EN-P - July 2013
Chapter 5
Frame 9 Mechanical Installation
Minimum Mounting
Clearances
Operating Temperatures
Frame 9 drives require a minimum of 1300 m
3
/h (765 cfm) of cooling air.
Nameplate Location
See
Figure 15
on page
65
.
400.0 mm
(15.75 in.)
80.0 mm
(3.2 in.)
50.0 mm
(1.97 in.)
350.0 mm
(13.8 in.)
400.0 mm
(15.75 in.)
350.0 mm
(13.8 in.)
50.0 mm
(1.97 in.)
See
Figure 15
on page
65
for detailed dimension information.
PowerFlex Drive
Voltage Class
Amp Rating
Surrounding Air Temperature
Normal Duty
Heavy Duty
700H
All
All
0…40
°
C
(32…104
°
F)
0…50
°
C
(32 to 122
°
F)
700S
400/480V AC
(540/650V DC)
All
0…40
°
C
(32…104
°
F)
0…40
°
C
(32…104
°
F)
600/690V AC
(810/932V DC)
170
0…40
°
C
(32…104
°
F)
0…40
°
C
(32…104
°
F)
208
0…35
°
C
(32…95
°
F)
0…40
°
C
(32…104
°
F)