beautypg.com

Minimum mounting clearances, Operating temperatures, Nameplate location – Rockwell Automation 20D PowerFlex 700H and 700S Frame 9...14 Drives User Manual

Page 64: Minimum mounting clearances operating temperatures

background image

64

Rockwell Automation Publication PFLEX-IN006E-EN-P - July 2013

Chapter 5

Frame 9 Mechanical Installation

Minimum Mounting
Clearances

Operating Temperatures

Frame 9 drives require a minimum of 1300 m

3

/h (765 cfm) of cooling air.

Nameplate Location

See

Figure 15

on page

65

.

400.0 mm
(15.75 in.)

80.0 mm

(3.2 in.)

50.0 mm
(1.97 in.)

350.0 mm

(13.8 in.)

400.0 mm

(15.75 in.)

350.0 mm

(13.8 in.)

50.0 mm

(1.97 in.)

See

Figure 15

on page

65

for detailed dimension information.

PowerFlex Drive

Voltage Class

Amp Rating

Surrounding Air Temperature
Normal Duty

Heavy Duty

700H

All

All

0…40

°

C

(32…104

°

F)

0…50

°

C

(32 to 122

°

F)

700S

400/480V AC
(540/650V DC)

All

0…40

°

C

(32…104

°

F)

0…40

°

C

(32…104

°

F)

600/690V AC
(810/932V DC)

170

0…40

°

C

(32…104

°

F)

0…40

°

C

(32…104

°

F)

208

0…35

°

C

(32…95

°

F)

0…40

°

C

(32…104

°

F)

This manual is related to the following products: