beautypg.com

Analog i/o configuration, Hardware enable circuitry, Analog i/o configuration hardware enable circuitry – Rockwell Automation 20D PowerFlex 700H and 700S Frame 9...14 Drives User Manual

Page 36

background image

36

Rockwell Automation Publication PFLEX-IN006E-EN-P - July 2013

Chapter 2

Control Wiring for PowerFlex 700H Drives

Analog I/O Configuration

See

Figure 6

on page

33

for the location of the jumpers indicated in the table

below.

Table 11 - I/O Configuration

Hardware Enable Circuitry

By default, the user can program a digital input as an Enable input. The status of
this input is

interpreted by drive software. If the application requires the drive to be

disabled

without software interpretation, a “dedicated” hardware enable

configuration can be utilized. This is done by removing jumper J5 (see table
below) and wiring the enable input to digital input 6. Verify that parameter 366
[Digital In6 Sel] is set to “1-Enable”.

Table 12 - Hardware Enable Configuration

IMPORTANT

Analog I/O must be configured through programming, as well as the jumpers
shown below. See the PowerFlex 700H Adjustable Frequency AC Drive
Programming Manual, publication

20C-PM001

.

Signal

Jumper

Setting

Analog
Inputs

J1 (Analog In 1)
J2 (Analog In 2)

0…20 mA

0…10V

±

10V

Analog
Outputs

J3 (Analog Out 1)
J4 (Analog Out 2)

0…20 mA

0…10V

±

10V

Signal

Jumper

Setting

Hardware
Enable

J5

Hardware Enable

Input Programmable (No Hardware Enable)

C D

B

A

J1

J2

C D

B

A

C D

B

A

J1

J2

C D

B

A

C D

B

A

J1

J2

C D

B

A

C D

B

A

J3

J4

C D

B

A

C D

B

A

J3

J4

C D

B

A

C D

B

A

J3

J4

C D

B

A

B

A

J5

B

A

J5

This manual is related to the following products: