beautypg.com

Rockwell Automation 20D PowerFlex 700H and 700S Frame 9...14 Drives User Manual

Page 39

background image

Rockwell Automation Publication PFLEX-IN006E-EN-P - July 2013

39

Control Wiring for PowerFlex 700H Drives

Chapter 2

2-Wire Control Non-
Reversing

(1)

24V DC internal supply

Disable Digital Input:#1:

Parameter 361 [Digital In1 Sel] = 0 “Not
Used”

Set Digital Input #2:

Parameter 362 [Digital In2 Sel] = 7 “Run”

Set Direction Mode:

Parameter 190 [Direction Mode] = 0
“Unipolar”

2-Wire Control
Reversing

(1)

External supply
(I/O board dependent)

Set Digital Input:#1:

Parameter 361 [Digital In1 Sel] = 8 “Run
Forward”

Set Digital Input #2:

Parameter 362 [Digital In2 Sel] = 9 “Run
Reverse”

3-Wire Control
Internal supply

No Changes Required

3-Wire Control
External supply
(I/O Board dependent). Requires
3-wire functions only ([Digital
In1 Sel]). Using 2-wire selections
will cause a type 2 alarm.

No Changes Required

Digital Output
Relays shown in powered state
with drive faulted. See

Table 10

on page

35

.

Two relays at terminals 24…26.

Select Source to Activate:

Parameters 380 [Digital Out1 Sel] / 384
[Digital Out2 Sel]

Enable Input

Configure with parameter 366 [Digital In6

Sel]
For dedicated hardware Enable:
Remove Jumper J5 (see page

36

)

(1) Important: Programming inputs for 2 wire control deactivates all HIM Start buttons unless parameter 192 [Save HIM Ref], bit 1

“Manual Mode” = “1.” This will allow the HIM to control Start and Jog.

Input/Output

Connection Example

Required Parameter Changes

12

17

20

19

Stop-Run

12

17

11

Run Rev.

Run Fwd.

115V/
+24V

Neutral/

Common

12

17

20

11

19

Start

Stop

12

17

11

Start

Stop

115V/

+24V

Neutral/

Common

21

24

Power Source

Fault
NOT Fault

NOT Run
Run

or

22

25

23

26

16

This manual is related to the following products: