Control Wiring for PowerFlex 700H Drives
Chapter 2
2-Wire Control Non-
Reversing
(1)
24V DC internal supply
• Disable Digital Input:#1:
Parameter 361 [Digital In1 Sel] = 0 “Not
Used”
• Set Digital Input #2:
Parameter 362 [Digital In2 Sel] = 7 “Run”
• Set Direction Mode:
Parameter 190 [Direction Mode] = 0
“Unipolar”
2-Wire Control
Reversing
(1)
External supply
(I/O board dependent)
• Set Digital Input:#1:
Parameter 361 [Digital In1 Sel] = 8 “Run
Forward”
• Set Digital Input #2:
Parameter 362 [Digital In2 Sel] = 9 “Run
Reverse”
3-Wire Control
Internal supply
• No Changes Required
3-Wire Control
External supply
(I/O Board dependent). Requires
3-wire functions only ([Digital
In1 Sel]). Using 2-wire selections
will cause a type 2 alarm.
• No Changes Required
Digital Output
Relays shown in powered state
with drive faulted. See
Table 10
on page
35
.
Two relays at terminals 24…26.
• Select Source to Activate:
Parameters 380 [Digital Out1 Sel] / 384
[Digital Out2 Sel]
Enable Input
• Configure with parameter 366 [Digital In6
Sel]
For dedicated hardware Enable:
Remove Jumper J5 (see page
(1) Important: Programming inputs for 2 wire control deactivates all HIM Start buttons unless parameter 192 [Save HIM Ref], bit 1
“Manual Mode” = “1.” This will allow the HIM to control Start and Jog.
Input/Output
Connection Example
Required Parameter Changes
12
17
20
19
Stop-Run
12
17
11
Run Rev.
Run Fwd.
115V/
+24V
Neutral/
Common
12
17
20
11
19
Start
Stop
12
17
11
Start
Stop
115V/
+24V
Neutral/
Common
21
24
Power Source
Fault
NOT Fault
NOT Run
Run
or
22
25
23
26
16