Rockwell Automation 20D PowerFlex 700H and 700S Frame 9...14 Drives User Manual
Page 164

164
Rockwell Automation Publication PFLEX-IN006E-EN-P - July 2013
Appendix A
Specifications
Category
Specification
PowerFlex 700H
PowerFlex 700S
Protection
Drive
380/400V
480V
500V
600V
690V
380/400V
480V
500V
600V
690V
AC Input Overvoltage Trip:
611V AC
611V AC
611V AC
806V AC
806V AC
675V AC
675V AC
675V AC
889V AC
889V AC
AC Input Undervoltage Trip:
235VAC
235VAC
235VAC
326VAC
326VAC
Adjustable
Bus Overvoltage Trip:
911VDC
911VDC
911VDC
1200V DC
1200V DC
911VDC
911VDC
911VDC
1200V DC
1200V DC
Bus Undervoltage Shutoff/Fault:
333VDC
333VDC
333VDC
461VDC
461VDC
Adjustable
Nominal Bus Voltage (Full Load):
517VDC
621VDC
645VDC
776VDC
890VDC
540VDC
648VDC
645VDC
810VDC
931V DC
Heat Sink Thermistor:
Monitored by microprocessor overtemp trip
Monitored by microprocessor overtemp trip
Drive Overcurrent Trip
Software Overcurrent Trip:
Hardware Overcurrent Trip:
Instantaneous Current Limit:
—
360% of rated Heavy Duty current (typical)
—
Calculated value, 105% of motor rated to 200% of drive rated
360% of rated Heavy Duty current (typical)
—
Line transients:
up to 6000 volts peak per IEEE C62.41-1991
Up to 6000 volts peak per IEEE C62.41-1991
Control Logic Noise Immunity:
Showering arc transients up to 1500V peak
Showering arc transients up to 1500V peak
Power Ride-Thru:
15 milliseconds at full load
15 milliseconds at full load
Logic Control Ride-Thru:
0.5 seconds minimum, 2 seconds typical
0.25 seconds, drive not running
Ground Fault Trip:
Phase-to-ground on drive output
Phase-to-ground on drive output
Short Circuit Trip:
Phase-to-phase on drive output
Phase-to-phase on drive output
Environment
Altitude:
1000 m (3300 ft.) maximum without derating. Derate the drive by 1% for every
100 m (328 ft.) above 1000 m (3300 ft.).
1000 m (3300 ft.) maximum without derating. Derate the drive by 1% for every
100 m (328 ft.) above 1000 m (3300 ft.).
Maximum Surrounding Air Temperature without
De-rating:
Based on drive rating, refer to Drive Ratings on page
Based on drive rating, refer to Drive Ratings on page
Storage Temperature (all const.):
–40 to 60° C (–40 to 140° F)
–40 to 70° C (–40 to 158° F)
Atmosphere:
Important: Drive must not be installed in an area where the ambient
atmosphere contains volatile or corrosive gas, vapors or dust. If the drive is not
going to be installed for a period of time, it must be stored in an area where it
will not be exposed to a corrosive atmosphere.
Important: Drive must not be installed in an area where the ambient
atmosphere contains volatile or corrosive gas, vapors or dust. If the drive is not
going to be installed for a period of time, it must be stored in an area where it
will not be exposed to a corrosive atmosphere.
Relative Humidity:
5 to 95% non-condensing
5 to 95% non-condensing
Shock:
Non-operational
15G peak for 11ms duration (
±
1.0 ms)
15G peak for 11ms duration (
±
1.0 ms)
Vibration:
2 mm (0.0787 in.) displacement, 1G peak
EN50178 / EN60068-2-6
2 mm (0.0787 in.) displacement, 1G peak
EN50178 / EN60068-2-6
Sound:
Frame
Sound Level
Back- ground
Noise Level
Note: Sound pressure level is
measured at 1 meter. All
devices measured are 400V
IP21 and in power up mode.
Frame
Sound Level
Back- ground
Noise Level
Note: Sound pressure level is
measured at 1 meter. All
devices measured are 400V
IP21 and in power up mode.
9
78 dba
49 dba
9
78 dba
49 dba
10
77 dba
49 dba
10
77 dba
49 dba
13
76d ba
46 dba
13
76d ba
46 dba
Electrical
AC Input Voltage Tolerance:
±
10%
±
10%
Frequency Tolerance:
47…63 Hz.
47…63 Hz.
Input Phases:
Three-phase input provides full rating for all drives. Single-phase operation
provides 50% of rated current.
Three-phase input provides full rating for all drives. Single-phase operation
provides 50% of rated current.
Displacement Power Factor:
0.98 across entire speed range.
0.98 across entire speed range.
Efficiency:
97.5% at rated amps, nominal line volts.
97.5% at rated amps, nominal line volts.
Maximum Short Circuit Rating:
≤
200,000 Amps symmetrical.
≤
200,000 Amps symmetrical.
Actual Short Circuit Rating:
Determined by AIC rating of installed fuse/circuit breaker.
Determined by AIC rating of installed fuse/circuit breaker.
Maximum Drive to Motor Power Ratio:
Recommended not greater than 2:1 ratio.
Drive to motor rating cannot exceed a 2:1 ratio.