DC Input Precharge Control Wiring
If you are installing a DC input drive with a precharge interlock you must make
the following connections on the X50 terminal block from the precharge circuit.
See
Figure 1
on page
27
for additional wiring information.
Table 3 - Frame 9 - X50 Terminal Block Connections
Table 4 - Frames 10…14 - X50 Terminal Block Connections
Table 5 - X50 Terminal Block Specifications (All Frame Sizes)
X50 Terminal Block
Terminal
Description
1
Charge Relay Contact
2
Charge Relay Contact
5
Precharge Complete Signal (+24V DC)
6
Precharge Complete Signal (Common)
X50 Terminal Block
Frame
Terminal
Precharge Circuit Connection Description
10, 11 & 13
21
Charge Relay Contact
23
Charge Relay Contact
25
Precharge Complete Signal (+24V DC)
26
Precharge Complete Signal (Common)
12 & 14
Power Structure 1
21
Charge Relay Contact
23
Charge Relay Contact (Jumper to Power Structure 2
Terminal 21)
25
Precharge Complete Signal (+24V DC)
26
Precharge Complete Signal (Common)
Power Structure 2
21
Charge Relay Contact (Jumper to Power Structure 1
Terminal 23)
23
Charge Relay Contact
25
Precharge Complete Signal (+24V DC)
26
Precharge Complete Signal (Common)
Wire Size Range
(1)
(1) Maximum/minimum sizes that the terminal block will accept - these are not recommendations.
Torque
Maximum
Minimum
Recommended
6.0 mm
2
(10 AWG)
1.0 mm
2
(18 AWG)
0.8 N
•
m (7.0 lb
•
in)