beautypg.com

Rockwell Automation 20D PowerFlex 700H and 700S Frame 9...14 Drives User Manual

Page 35

background image

Rockwell Automation Publication PFLEX-IN006E-EN-P - July 2013

35

Control Wiring for PowerFlex 700H Drives

Chapter 2

Table 10 - I/O Terminal Designations

No.

Signal

Factory Default

Description

Related
Parameter(s)

1

Analog Input 1 (–)

(1)

(2)

Isolated

(3)

, bipolar, differential, 9 bit & sign, 88 k

Ω

input impedance. A

jumper (page

36

) selects: 0…10V, ±10V,

0…20 mA. Default: 0…10V (Ri =200k), 4…20 mA (Ri=100

Ω

).

320…327

2

Analog Input 1 (+)

(1)

3

Analog Input 2 (–)

(1)

4

Analog Input 2 (+)

(1)

5

–10V Pot Reference

2 k

Ω

minimum, 10 mA maximum load, 1% accuracy.

6

Pot Common (GND)

For (+) and (–) 10V pot references.

7

+10V Pot Reference

2 k

Ω

minimum, 10 mA maximum load, 1% accuracy.

8

Analog Output 1 (+)

(2)

Bipolar (current out is not bipolar), 9 bit and sign, 2 k

Ω

minimum load. A

jumper (page

36

) selects: 0…10V, ±10V, 0…20 mA.

340…347

9

Analog Output Common

10

Analog Output 2 (+)

11

Digital Input 1

Stop - CF

115V AC, 50/60 Hz - Opto isolated
Low State: less than 30V AC
High State: greater than 40V AC
24V DC - Opto isolated (250V)
Low State: less than 5V DC
High State: greater than 20V DC
11.2 mA DC
Enable: Digital Input 6 is jumper selectable for HW Enable (see page

36

).

On-Time: < 16.7 ms, Off-Time < 1 ms

361…366

12

Digital Input 2

Start

13

Digital Input 3

Auto/Man

14

Digital Input 4

Speed Sel 1

15

Digital Input 5

Speed Sel 2

16

Digital Input 6/Hardware Enable

Speed Sel 3

17

Digital Input Common

Allows source or sink operation. Terminals 17, 18 and 19 can also be used
to provide backup power to DPI and control devices.

18
19

+24VDC

(4)

Drive supplied logic input power.

20

24V Common

(4)

Common for internal power supply.

21

Digital Output 1 – N.C.

(5)

Fault

Max. Resistive Load:
240V AC/30V DC – 1200VA, 150 W
Max. Current: 5 A, Min. Load: 10 mA
Max. Inductive Load:
240V AC/30V DC – 840VA, 105 W
Max. Current: 3.5 A, Min. Load: 10 mA

380…391

22

Digital Output 1 Common

23

Digital Output 1 – N.O.

(5)

NOT Fault

24

Digital Output 2 – N.C.

(5)

NOT Run

25

Digital Output 2/3 Com.

26

Digital Output 3 – N.O.

(5)

Run

(1) Important: Input must be configured with a jumper. Drive damage may occur if jumper is not installed properly. See page

36

.

(2) These inputs/outputs are dependant on a number of parameters (see “Related Parameters” column in table).
(3) Differential Isolation - External source must be maintained at less than 160V with respect to PE. Input provides high common mode immunity.
(4) 150 mA maximum load. Not present on 115V versions. Can be used to provide control power from an external 24V source when main power is not applied. See page

36

.

(5) Contacts in un-powered state. Any relay programmed as Fault or Alarm will energize (pick up) when power is applied to drive and de-energize (drop out) when a fault or alarm exists. Relays selected for

other functions will energize only when that condition exists and will de-energize when condition is removed.

1

10

20

21

This manual is related to the following products: