QUICK START
49’1340 e
FlexPak 3000
6-5
Table 6.2 - Quick Start Parameter Modification Sequence. - continued
Step
No.
Parameter
Name
Code
No.
Default Description
User
Setting
9 ACCELERA-
TION RATE
001
5 SEC.
The time it takes to accelerate from 0 to Top
speed. Smaller changes in speed take
proportionately less time. If
TRIM MODE
SELECT
is set to
PROPORTIONAL
, this time
value is modified by
DRAW PERCENTAGE
OUT.
10 DECELERA-
TION RATE
002 5
SEC.
DECELERATION TIME
selects the time it takes
to decelerate from Top speed to 0. Smaller
changes in speed take proportionately less
time. If
TRIM MODE SELECT
is set to
PROPORTIONAL
, this time value is modified by
DRAW PERCENTAGE OUT.
11 MINIMUM
SPEED
003 0
RPM
ATTENTION: This drive can operate at and
maintaining zero speed when this parameter
is set to zero. The user is responsible for
assuring safe conditions for operating
personnel by providing suitable guards,
audible or visual alarms, or other devices to
indicate that the drive is operating at or near
zero speed. Failure to observe this
precaution could result in severe bodily injury
or loss of life.
Selects the minimum speed of the drive
without being stopped. It is typically greater
than zero. If it is < 10% of MAXIMUM SPEED,
an alarm is generated.
12 MAXIMUM
SPEED
004 500
RPM The maximum speed of the drive that can be
supported by the application or process.
If raising this value causes
MINIMUM SPEED
to
become less than 10% of
MAXIMUM
SPEED
,
an alarm is generated.
This is typically set to base speed from the
motor nameplate.
ATTENTION: Do not allow the motor to
exceed the maximum safe speed as
determined by the equipment manufacturer
of the motor or the driven equipment.
Failure to observe these precautions could
result in bodily injury.
13 JOG
ACCEL/
DECEL RATE
013
3 SEC.
The time it takes the Jog reference circuit to
reach
TOP SPEED (P.011)
from zero. The
S-
CURVE ROUNDING (P.014)
parameter does not
affect the setting of this parameter.