QUICK START

49’1340 e

FlexPak 3000

6-5

Table 6.2 - Quick Start Parameter Modification Sequence. - continued

Step
No.

Parameter
Name

Code
No.

Default Description

User
Setting

9 ACCELERA-

TION RATE

001

5 SEC.

The time it takes to accelerate from 0 to Top
speed. Smaller changes in speed take
proportionately less time. If

TRIM MODE

SELECT

is set to

PROPORTIONAL

, this time

value is modified by

DRAW PERCENTAGE

OUT.

10 DECELERA-

TION RATE

002 5

SEC.

DECELERATION TIME

selects the time it takes

to decelerate from Top speed to 0. Smaller
changes in speed take proportionately less
time. If

TRIM MODE SELECT

is set to

PROPORTIONAL

, this time value is modified by

DRAW PERCENTAGE OUT.

11 MINIMUM

SPEED

003 0

RPM

ATTENTION: This drive can operate at and
maintaining zero speed when this parameter
is set to zero. The user is responsible for
assuring safe conditions for operating
personnel by providing suitable guards,
audible or visual alarms, or other devices to
indicate that the drive is operating at or near
zero speed. Failure to observe this
precaution could result in severe bodily injury
or loss of life.

Selects the minimum speed of the drive
without being stopped. It is typically greater
than zero. If it is < 10% of MAXIMUM SPEED,
an alarm is generated.

12 MAXIMUM

SPEED

004 500

RPM The maximum speed of the drive that can be

supported by the application or process.
If raising this value causes

MINIMUM SPEED

to

become less than 10% of

MAXIMUM

SPEED

,

an alarm is generated.

This is typically set to base speed from the
motor nameplate.

ATTENTION: Do not allow the motor to
exceed the maximum safe speed as
determined by the equipment manufacturer
of the motor or the driven equipment.
Failure to observe these precautions could
result in bodily injury.

13 JOG

ACCEL/

DECEL RATE

013

3 SEC.

The time it takes the Jog reference circuit to
reach

TOP SPEED (P.011)

from zero. The

S-

CURVE ROUNDING (P.014)

parameter does not

affect the setting of this parameter.