Rockwell Automation FlexPak 3000 Power Module SW-Version 4.3 User Manual
Page 127
APPENDIX B
49’1340 e
FlexPak 3000
B-23
JOG ACCEL/DECEL TIME (P.013)
Sets the time it takes the jog reference circuit to reach TOP SPEED from zero.
The S-CURVE ROUNDING parameter does not affect the setting of this parameter.
Parameter Range:
0.1 to 300.0 seconds (actual minimum setting based on connected inertia)
Default Setting:
3.0
seconds
Parameter Type:
Tuneable
OIM Menu Path(s):
Drive Reference - Drive Reference Ramp - Quick Start
JOG OFF DELAY TIME (P.121)
The minimum delay between removing the jog input and opening the contactor.
Release of the Jog input will not cause the contactor to open until the speed feedback is less than or
equal to STOP SPEED THRESHOLD or until the JOG OFF DELAY TIME has been exceeded,
whichever occurs last. The purpose of this delay is to reduce the wear on the contactor when repeatedly
opening and closing the JOG input in a short period of time.
Parameter Range:
0.0 to 10.0 seconds
Default Setting:
1.0
seconds
Parameter Type:
Configurable
OIM Menu Path(s):
Drive Reference - Drive Reference Configure
Refer also to Parameters:
JOG ACCEL/DECEL TIME (P.013)
JOG SPEED 1 (P.012)
JOG SPEED 2 (P.017),
STOP SPEED THRESHOLD (P.113)
JOG SPEED 1 (P.012)
The operating speed while the drive is in jogging.
Parameter Range:
0 to MAXIMUM SPEED (RPM or user-defined units)
Default Setting:
250 (RPM or user-defined units)
Parameter Type:
Tuneable
OIM Menu Path(s):
Drive Reference - Drive Reference Configure - Quick Start
Refer also to Parameter:
DIG IN 0 SELECT(P.428),
JOG SPEED 2 (P.017)
If DIG IN 0 SELECT (P.428) is set to JOG SPEED SELECT, this parameter is used when DIG IN 0
(regulator terminal 12) is OFF.
if DIG IN 0 SELECT is not set to JOG SPEED SELECT only JOG SPEED 1 (P.012) is used.
JOG SPEED 2 (P.017)
The operating speed when the drive is jogging. If DIG IN 0 SELECT (P.428) is set to JOG SPEED
SELECT and DIG IN 0 (regulator terminal 12) is ON. Switching between the two jog speeds while
jogging will cause the drive to accelerate or decelerate to the new jog speed at the rate set by JOG
ACCEL/DECEL TIME (P.013). JOG SPEED 1 will be used for all other choices of DIG IN 0 SELECT.
Parameter Range:
0 to MAXIMUM SPEED (RPM or user-defined units)
Default Setting:
250 (RPM or user-defined units)
Parameter Type:
Tuneable
OIM Menu Path(s):
Additional
Parameters
Refer also to Parameter:
DIG IN 0 SELECT(P.428),
JOG SPEED 1 (P.012)