METER OUT 1 SELECT (P.404)
Selects the drive testpoint that will source meter output 1 (terminals 24 and 25 on the regulator board).
Parameter Range:
See table below for parameter options.
Default Setting:
CML
FEEDBACK
Parameter Type:
Tuneable
OIM Menu Path(s):
Input/Output - Meter Outputs
Signal Selected
Full Scale Value
CML FEEDBACK (P.397)
CML REFERENCE (P.396)
CML ERROR (P.398)
SPD LOOP OUTPUT (P.299)
±
MOTOR RATED ARM AMPS * MAXIMUM CURRENT
100
SPD LOOP FEEDBACK (P.296)
SPD LOOP REFERENCE (P.295)
SPD LOOP ERROR (P.297)
SPEED RAMP OUTPUT (P.199)
SPEED RAMP INPUT TP (P.198)
SPD SOURCE SELECT OUT (P.193)
TRIM OUTPUT (P.197)
ANALOG TACH FEEDBACK (P.291)
PULSE TACH FEEDBACK (P.292)
OCL OUTPUT (P.848)
±
TOP SPEED
ARMATURE VOLTAGE (P.289)
±
MOTOR RATED ARM VOLTS
POWER OUTPUT
±
MOTOR RATED ARM VOLTS * MOTOR RATED ARM AMPS * MAXIMUM CURRENT
100
FIELD REFERENCE (P.590)
FIELD FEEDBACK (P.589)
MOTOR HOT FLD AMPS
OCL REFERENCE (P.845)
±
4095
OCL RAMP OUTPUT (P.846)
OCL FEEDBACK (P.847)
NETW IN REG 1 (P.905)
NETW IN REG 2 (P.906)
NETW IN REG 3 (P.907)
FULL SCALE
ZERO 0
METER OUT 1 ZERO ADJ (P.402)
Removes any hardware-introduced offset from the Meter 1 output signal at the regulator board terminals.
Parameter Range:
-200 to + 200
Default Setting:
0
Parameter Type:
Tuneable
OIM Menu Path(s):
Input/Output - Meter Outputs
NOTE: Testpoint METER OUT ZERO must source METER OUT 1 SELECT for an accurate adjustment. See Appendix D,
figure D.8, for further details.