Rockwell Automation FlexPak 3000 Power Module SW-Version 4.3 User Manual

Page 66

background image

QUICK START

FlexPak 3000 49’1340

e

6-4

Table 6.2 - Quick Start Parameter Modification Sequence. - continued

Step
No.

Parameter
Name

Code
No.

Default Description

User
Setting

3 MOTOR

RATED ARM
VOLTS

009 400

VOLTS The rated armature voltage from the motor

nameplate.

4 REVERSE

DISABLE

015 OFF*

NOTE:

This parameter might be affected by

FEEDBACK SELECT

, step 5.

When

ON

,

REVERSE DISABLE

prevents the

speed reference from dropping below zero.
The reverse bridge cannot be activated.
When OFF, the speed reference can drop
below zero and the drive can reverse.
*The default is ON when:

The drive has a non-regen. (S6) power unit.

FEEDBACK SELECT

is set to

AC TACH

.

FEEDBACK SELECT

is set to

PULSE TACH

and

PULSE TACH QUADRATURE

is OFF.

5 FEEDBACK

SELECT

200

ARMATURE
VOLT

Determines the type of feedback signal that is
used for the speed/voltage loop:

PULSE TACH

can be selected only if a pulse

tachometer kit is installed.

FEEDBACK SELECT

causes the

NEGATIVE

CURRENT LIM

(step 16) to be set to 0 and

REVERSE DISABLE

to be set to ON if:

AC TACH

is selected.

PULSE TACH

is selected and

PULSE TACH

QUAD

is set OFF.

6 ANLG

TACH

VOLTS/1000

203 60

V/1000

RPM

Only needs to be set if

FEEDBACK SELECT

is

set to

AC TACH

or

DC TACH

.

This parameter is the analog tachometer
scaling from the tachometer nameplate in volts
per 1000 RPM.
It might be limited to less than 200.0
volts/1000 so that voltage from the tachometer
will not be more than 250 V.

7 PULSE

TACH

PPR

207 1024

PPR

Only displayed if

FEEDBACK SELECT

Is set to

PULSE TACH

and a pulse tach interface is

installed.
It sets the pulse encoder pulses per revolution
(PPR) from the pulse encoder nameplate.

8 PULSE

TACH

QUADRA-
TURE

208 ON

Only displayed if

FEEDBACK

SELECT

is set to

PULSE TACH

and a pulse tach interface is

installed. Enables or disables pulse encoder
quadrature.
Set ON for a bi-directional pulse encoder.
Set OFF for a unidirectional pulse encoder.
If

PULSE TACH QUADRATURE

is set to

OFF

while

PULSE TACH

is the selected

FEEDBACK

SELECT

type, NEGATIVE

CURRENT

LIM

will

be set to 0 and

REVERSE

DISABLE

set to ON

(preventing reverse direction).