G - user quick reference table, User quick reference table – Rockwell Automation FlexPak 3000 Power Module SW-Version 4.3 User Manual
Page 201
![background image](/manuals/581087/201/background.png)
APPENDIX G
49’1340 e
FlexPak 3000
G-1
User Quick Reference Table
Table G.1 - User Quick Reference Table for Input Parameters
Par.
Parameter
Parameter Selection /
Pg.
Initial Factory
User Data
No.
Adjustment
Range
B-
Setting
Date
Setting
000
CONTROL SOURCE SELECT
•
KEYPAD
•
SERIAL
•
TERMBLK
•
NETWORK
11
KEYPAD
001 ACCELERATION
TIME
0.1
- 300.0 sec
1
5.0 sec
002 DECELERATION
TIME
0.1
- 300.0 sec
12
5.0 sec
003
MINIMUM SPEED
0 - MAXIMUM SPEED (P.004)
29
0 (*RPM)
004
MAXIMUM SPEED
1 - TOP SPEED (P.011)
26
500 (*RPM)
005
POSITIVE CURRENT LIM
0 - MAXIMUM CURRENT
(P.007) in % FLA (P.008)
43
150% P.008
006
NEGATIVE CURRENT LIM
0 - MAXIMUM CURRENT
(P.007) in % FLA (P.008)
32
150% P.008
007
MAXIMUM CURRENT
25 - 200 %FLA (P.008)
25
150% P.008
008
MOTOR RATED ARM AMPS
0 - 3000.0 A
31
unit type dep.
009
MOTOR RATED ARM VOLTS
160 - 675 VDC or
240 - 1000 VDC (type 690 VAC)
31
400 V
010
CT TURNS RATIO
•
25 A Unit:
208
•
60 A Unit:
416
•
150 A Unit:
833
•
250 A Unit:
2000
•
450 A Unit:
3000
•
800 A Unit:
5230
•
1200 A Unit:
8000
•
1600-2000 A Unit:
10500
11
depending on
unit type
32767 Tp/Tn
011
TOP SPEED
5 - 5000 RPM
51
500 RPM
012
JOG SPEED 1
0 - MAXIMUM SPEED (P.004)
in *rpm
23
250 (*RPM)
013
JOG ACCEL/DECEL TIME
0.1 - 300.0 sec
23
3.0 sec
014
S-CURVE ROUNDING
0 - 50% (0% = no rounding)
45
0%
015 REVERSE
DISABLE
•
OFF
•
ON
44
S-6R = OFF
S-6 = ON
017
JOG SPEED 2
0 - MAXIMUM SPEED (P.004)
in *rpm
23
250 (*RPM)
018
RAMP STOP DECEL TIME
0.1 - 300.0 sec
44
5.0 sec
019
SPD LOOP SCAN TIME
0 = 5 msec
1 = 10 msec
49
5 msec
Analog Inputs
100
(2)
ANLG AUTO SIGNAL TYPE
•
0 -10 V
• ±
10 V
•
4-20 mA
•
10-50 mA
2 0-10
V
101
ANLG AUTO GAIN ADJ
0.750 - 1.250
2
1.000
102
ANLG AUTO ZERO ADJ
-200 - +200
2
0
103
AUTO REFERENCE SELECT
•
ANALOG
•
FREQUENCY IN
8 ANALOG
104
ANLG MAN REF GAIN ADJ
0.750 - 1.250
4
1.000
(*) Or user defined unit.
(2) Jumpers J10 and J12 must be set for the type of auto reference selected.