beautypg.com

Rockwell Automation FlexPak 3000 Power Module SW-Version 4.3 User Manual

Page 115

background image

APPENDIX B

49’1340 e

FlexPak 3000

B-11

CONTROL SOURCE SELECT (P.000)

This parameter is only available on the Drive Configuration Module (DCM). It is a key on the OIM.
CONTROL SOURCE SELECT selects the source for the drive control signal. The control source options
are KEYPAD, SERIAL, TERMBLK, or NETWORK. If the drive is configured as a current (torque)
regulator (jumper J15 is set to current), only TERMBLK or NETWORK can be selected.

Parameter Range:

KEYPAD,

SERIAL,

TERMBLK,

NETWORK

Default Setting:

KEYPAD

Parameter Type:

Configurable

Menu Path(s):

Key CSS on the OIM.

When KEYPAD is selected, the OIM keys control the drive and the OIM drive reference is used.
The KEYPAD REF value (displayed on the first monitor mode screen) is used as the drive reference.

When TERMBLK is selected, the signals at the regulator board terminals 16 through 20 are used for
control. See section 3 for information on wiring the terminal strip.

When NETWORK is selected, the Control is through a network such as the AutoMax Network
Communication kit, DeviceNet Interface kit, or ControlNet Network Communication kit.

When SERIAL is selected, control is through a personal computer running the CS3000 software.

Important

: When switching the control source from

NETWORK

to any other option, the internal multiplexer

selection parameters that use

NETW IN REG

1, 2, and 3, are not affected. Therefore, any

selection that was set to

NETW IN REG

# will remain, and the data in

NETW IN REG

1, 2, 3 will be

the value used in the control path. (Note that these parameters contain the last data received
from the network before the control source was switched and will no longer be updated from
the network.) To change this, you must reconfigure any affected selection parameters.

CT TURNS RATIO (P.010)

Parameter Range:

1 to 32767

Default Setting:

Depending on unit type

Parameter Type:

Configurable

OIM Menu Path(s):

Current Minor Loop (CML) - CML Feedback Scaling

CAUTION

:

This parameter is also used in the calculation of the burden resistor value. Do not adjust/change the
value of this parameter from its factory default value unless you are replacing the regulator board.
Failure to observe this precaution could result in damage to, or destruction of, the equipment.

The drive current transformer turns ratio (Tp/Tn):

25 A Unit:

208

60 A Unit:

416

150 A Unit:

833

250 A Unit:

2000

450 A Unit:

3000

800 A Unit:

5230

1200 A Unit:

8000

1600-2000 A Unit:

10500

CURRENT COMPOUNDING (P.209)

Sets the level of current compounding to be used during any mode of drive operation.

Parameter Range:

-50% to + 50%

Default Setting:

0%

Parameter Type:

Tuneable

OIM Menu Path(s):

Speed/Voltage Loop (SPD) - Speed Voltage Loop (SPD) Tuning