Din rail mounting – Rockwell Automation 2080-LC50 Micro830 and Micro850 Programmable Controllers User Manual User Manual
Page 37
Rockwell Automation Publication 2080-UM002F-EN-E - December 2013
23
Install Your Controller Chapter 3
Micro850 48-Point Controllers
2080-LC50-48AWB, 2080-LC50-48QWB, 2080-LC50-48QBB, 2080-LC50-48QVB
Maintain spacing from objects such as enclosure walls, wireways and adjacent
equipment. Allow 50.8 mm (2 in.) of space on all sides for adequate ventilation. If
optional accessories/modules are attached to the controller, such as the power
supply 2080-PS120-240VAC or expansion I/O modules, make sure that there is
50.8 mm (2 in.) of space on all sides after attaching the optional parts.
DIN Rail Mounting
The module can be mounted using the following DIN rails: 35 x 7.5 x 1 mm
(EN 50 022 - 35 x 7.5).
Before mounting the module on a DIN rail, use a flat-blade screwdriver in the
DIN rail latch and pry it downwards until it is in the unlatched position.
1.
Hook the top of the DIN rail mounting area of the controller onto the
DIN rail, and then press the bottom until the controller snaps onto the
DIN rail.
2.
Push the DIN rail latch back into the latched position.
Use DIN rail end anchors (Allen-Bradley part number 1492-EAJ35 or
1492-EAHJ35) for vibration or shock environments.
To remove your controller from the DIN rail, pry the DIN rail latch downwards
until it is in the unlatched position.
TIP
For environments with greater vibration and shock concerns, use the
panel mounting method, instead of DIN rail mounting.
45916
238 (9.37)
80 (3.15 )
90 (3.54)
Measurements in millimeters (inches)