B - quickstarts, Flash upgrade your micro800 firmware, Appendix c – Rockwell Automation 2080-LC50 Micro830 and Micro850 Programmable Controllers User Manual User Manual
Page 197: Quickstarts, Appendix
Rockwell Automation Publication 2080-UM002F-EN-E - December 2013
181
Appendix
C
Quickstarts
This chapter covers some common tasks and quickstart instructions that are
aimed to make you familiar with the in Connected Component Workbench. The
following quickstarts are included:
Flash Upgrade Your
Micro800 Firmware
This quick start will show you how to flash update the firmware in a Micro800
controller using ControlFLASH. ControlFLASH is installed or updated with
the latest Micro800 firmware when Connected Components Workbench
software is installed on your computer.
On Micro850 controllers, users can use flash upgrade their controllers through
the Ethernet port, in addition to the USB.
1. Through USB
: Verify successful RSLinx Classic communications with
your Micro800 controller by USB using RSWho. Micro810 12-pt.
controller uses the 12PtM810_xxxxx driver and the Micro830/Micro850
uses the AB_VBP-x driver.
Topic
Page
Flash Upgrade Your Micro800 Firmware
Establish Communications Between RSLinx and a Micro830/Micro850
Controller through USB
ATTENTION: All Ethernet settings are reverted to factory default after
a ControlFlash firmware upgrade. For users who need to use the same
static IP address as previously set, for example, use the Memory
Module to store project settings prior to a flash upgrade so that you
can have the option to restore your original Ethernet settings.