Troubleshooting Appendix E

0xF12z
(Note: z indicates
the logic axis ID.)

Motion configuration for axis z cannot be
supported by this controller model, or the axis
configuration has some resource conflict with
some other motion axis, which has been
configured earlier.

Perform the following:

Remove all axes and re-configure motion with the guidance from the User

Manual.

If fault is consistent, upgrade to the latest Connected Components

Workbench software revision.

0xF15z
(Note: z indicates
the logic axis ID.)

There is a motion engine logic error (firmware
logic issue or memory crash) for one axis
detected during motion engine cyclic operation.
One possible reason can be motion engine data/
memory crash.

Perform the following:

Clear the fault, and switch the controller to RUN mode again.

If fault is consistent, do power cycle for whole motion setup, including

controller, drive and moving mechanism.

Re-download the User Application.

0xF210

The expansion I/O terminator is missing.

Perform the following:

Power off the controller.

Attach the expansion I/O terminator on the last expansion I/O module on the

system.

Power on the controller.

0xF230

The maximum number of expansion I/O modules
has been exceeded.

Perform the following:

Power off the controller.

Check that the number of expansion I/O modules is not more than four.

Power on the controller.

0xF250

There is a non-recoverable error and the
expansion I/O module(s) could not be detected.

Perform the following:

Cycle power to your Micro800 controller.

If the error persists, contact your local Rockwell Automation technical support
representative. For contact information, see

http://support.rockwellautomation.com/MySupport.asp

.

0xF26z
(z indicates the
slot number of the
expansion I/O. If
z=0, then the slot
number cannot be
identified.)

An expansion I/O master fault is detected on the
system.

Perform the following:

Cycle power to your Micro800 controller.

If the error persists, contact your local Rockwell Automation technical support
representative. For contact information, see

http://support.rockwellautomation.com/MySupport.asp

.

0xF27z
(z indicates the
slot number of the
expansion I/O. If
z=0, then the slot
number cannot be
identified.)

A non-recoverable communication fault has
occurred on the expansion I/O module.

Perform the following:

Cycle power to the Micro800 controller, or

Replace the slot number z module.

If the error persists, contact your local Rockwell Automation technical support
representative. For contact information, see

http://support.rockwellautomation.com/MySupport.asp

.

0xF28z
(z indicates the
slot number of the
expansion I/O. If
z=0, then the slot
number cannot be
identified.)

Expansion I/O baudrate error.

Perform the following:

Cycle power to the Micro800 controller, or

Replace the slot number z module.

If the error persists, contact your local Rockwell Automation technical support
representative. For contact information, see

http://support.rockwellautomation.com/MySupport.asp

.

List of Error Codes for Micro800 controllers

Error Code

Description

Recommended Action