Troubleshooting Appendix E
0xF12z
(Note: z indicates
the logic axis ID.)
Motion configuration for axis z cannot be
supported by this controller model, or the axis
configuration has some resource conflict with
some other motion axis, which has been
configured earlier.
Perform the following:
• Remove all axes and re-configure motion with the guidance from the User
Manual.
• If fault is consistent, upgrade to the latest Connected Components
Workbench software revision.
0xF15z
(Note: z indicates
the logic axis ID.)
There is a motion engine logic error (firmware
logic issue or memory crash) for one axis
detected during motion engine cyclic operation.
One possible reason can be motion engine data/
memory crash.
Perform the following:
• Clear the fault, and switch the controller to RUN mode again.
• If fault is consistent, do power cycle for whole motion setup, including
controller, drive and moving mechanism.
• Re-download the User Application.
0xF210
The expansion I/O terminator is missing.
Perform the following:
• Power off the controller.
• Attach the expansion I/O terminator on the last expansion I/O module on the
system.
• Power on the controller.
0xF230
The maximum number of expansion I/O modules
has been exceeded.
Perform the following:
• Power off the controller.
• Check that the number of expansion I/O modules is not more than four.
• Power on the controller.
0xF250
There is a non-recoverable error and the
expansion I/O module(s) could not be detected.
Perform the following:
• Cycle power to your Micro800 controller.
If the error persists, contact your local Rockwell Automation technical support
representative. For contact information, see
.
0xF26z
(z indicates the
slot number of the
expansion I/O. If
z=0, then the slot
number cannot be
identified.)
An expansion I/O master fault is detected on the
system.
Perform the following:
• Cycle power to your Micro800 controller.
If the error persists, contact your local Rockwell Automation technical support
representative. For contact information, see
.
0xF27z
(z indicates the
slot number of the
expansion I/O. If
z=0, then the slot
number cannot be
identified.)
A non-recoverable communication fault has
occurred on the expansion I/O module.
Perform the following:
• Cycle power to the Micro800 controller, or
• Replace the slot number z module.
If the error persists, contact your local Rockwell Automation technical support
representative. For contact information, see
.
0xF28z
(z indicates the
slot number of the
expansion I/O. If
z=0, then the slot
number cannot be
identified.)
Expansion I/O baudrate error.
Perform the following:
• Cycle power to the Micro800 controller, or
• Replace the slot number z module.
If the error persists, contact your local Rockwell Automation technical support
representative. For contact information, see
.
List of Error Codes for Micro800 controllers
Error Code
Description
Recommended Action