150
Rockwell Automation Publication 2080-UM002F-EN-E - December 2013
Appendix A Specifications
Insulation stripping length
7 mm (0.28 in.)
Enclosure type rating
Meets IP20
North American temp code
T4
(1) Use this Conductor Category information for planning conductor routing. Refer to Industrial Automation Wiring and Grounding Guidelines, publication
Inputs
Attribute
High-Speed DC Input
(Inputs 0…3)
Standard DC Input
(inputs 4 and higher)
Number of Inputs
4
2
Input group to backplane isolation
Verified by one of the following dielectric tests: 1,414V DC for 2 s
75V DC working voltage (IEC Class 2 reinforced insulation)
Voltage category
24V DC sink/source
Off-state voltage, max
5V DC
On-state voltage , nom
24V DC
On-state voltage range
16.8…26.4V DC @ 65 °C (149 °F)
16.8…30.0V DC @ 30 °C (86 °F)
10…26.4V DC @ 65 °C (149 °F)
10…30.0V DC @ 30 °C (86 °F)
Off-state current, max
1.5 mA
On-state current, min
5.0 mA @ 16.8V DC
1.8 mA @ 10V DC
On-state current, nom
8.8 mA @ 24V DC
8.5 mA @ 24V DC
On-state current, max
12.0 mA @ 30V DC
Nominal impedance
3 k
Ω
3.74 k
Ω
IEC input compatibility
Type 3
AC input filter setting
8 ms for all embedded inputs
(In Connected Components Workbench, go to the Embedded I/O configuration window to reconfigure
the filter setting for each input group)
General – 2080-LC30-10QWB, 2080-LC30-10QVB
Attribute
2080-LC30-10QWB
2080-LC30-10QVB
Isolated AC Inputs (2080-LC30-10QWB, 2080-LC30-10QVB) (Inputs 0…3)
Attribute
Value
On-state voltage, nom
12/24V AC @ 50/60 Hz
Off-state voltage, min
4V AC @ 50/60Hz
Operating frequency, nom
50/60 Hz