beautypg.com

Rockwell Automation 2080-LC50 Micro830 and Micro850 Programmable Controllers User Manual User Manual

Page 171

background image

Rockwell Automation Publication 2080-UM002F-EN-E - December 2013

155

Specifications Appendix A

Load current, max

2.0 A

100 mA (high-speed
operation)
1.0 A @ 30 °C
0.3 A @ 65 °C (standard
operation)

1.0 A @ 30 °C
0.3 A @ 65 °C (standard
operation)

Surge current, per point

Refer to Relay Contacts Ratings on page 155

4.0 A every 1 s @ 30 °C; every 2 s @ 65 °C

(1)

Current, per common, max

5 A

Turn on time/
Turn off time, max

10 ms

2.5

μs

ON: 0.1 ms
OFF: 1 ms

(1) Applies for general purpose operation only. Does not apply for high-speed operation.

Outputs

Attribute

Relay Output
(2080-LC30-16AWB, 2080-LC30-16QWB only)

Hi-Speed Output
(2080-LC30-16QVB only)
(Outputs 0…1)

Standard Output
(2080-LC30-16QVB only)
(Outputs 2…5)

Relay Contacts Ratings

Maximum Volts

Amperes

Amperes
Continuous

Volt-Amperes

Make

Break

Make

Break

120V AC

15 A

1.5 A

2.0 A

1800V A

180V A

240V AC

7.5 A

0.75 A

24V DC

1.0 A

1.0 A

28V A

125V DC

0.22 A

Environmental Specifications

Attribute

Value

Temperature, operating

IEC 60068-2-1 (Test Ad, Operating Cold),
IEC 60068-2-2 (Test Bd, Operating Dry Heat),
IEC 60068-2-14 (Test Nb, Operating Thermal Shock):
-20…65 °C (-4…149 °F)

Temperature, surrounding air,
max

65 °C (149 °F)

Temperature, non-operating

IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold),
IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat),
IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock):
-40…85 °C (-40…185 °F)

Relative humidity

IEC 60068-2-30 (Test Db, Unpackaged Damp Heat):
5…95% non-condensing

Vibration

IEC 60068-2-6 (Test Fc, Operating):
2 g @ 10…500 Hz

Shock, operating

IEC 60068-2-27 (Test Ea, Unpackaged Shock):
25 g

Shock, nonoperating

IEC 60068-2-27 (Test Ea, Unpackaged Shock):
DIN mount: 25 g
PANEL mount: 45 g

Emissions

CISPR 11
Group 1, Class A