Edit axis configuration, General parameters – Rockwell Automation 2080-LC50 Micro830 and Micro850 Programmable Controllers User Manual User Manual
Page 105

Rockwell Automation Publication 2080-UM002F-EN-E - December 2013
91
Motion Control with PTO and PWM Chapter 7
Edit Axis Configuration
General Parameters
1.
On the axis configuration tree, click General.
The
2.
Edit General parameters. You can refer to the table for a description of the
general configuration parameters for a motion axis.
TIP
To help you edit these motion properties, see
. You can also learn more about axis configuration parameters.
IMPORTANT
To edit these general parameters, you can refer to
for more information about fixed and configurable
outputs.
General Parameters
Parameter
Description and Values
Axis Name
User defined. Provides a name for the motion axis.
PTO Channel
Shows the list of available PTO channels.
Pulse output
Presents the logical variable name of the Direction Output channel based
on the PTO channel value that has been assigned.
Direction output
Presents the logical variable name of the Direction Output channel based
on the PTO channel value that has been assigned.
Drive Enable Output
Servo On Output Enable flag. Check the option box to enable.
- Output
The list of available digital output variables that can be assigned as
servo/drive output.
- Active Level
Set as High (default) or Low.
In-position Input
Check the option box to enable in-position input monitoring.
- Input
List of digital input variables for in-position input monitoring.
Select an input.