Specifications Appendix A
Outputs
Attribute
2080-LC30-10QWB
2080-LC30-10QVB
Relay Output
Hi-Speed Output
(Outputs 0…1)
Standard Output
(Outputs 2…3)
Output voltage, min
5V DC, 5V AC
10.8V DC
10V DC
Output voltage, max
125V DC, 265V AC
26.4V DC
26.4V DC
Load current, min
10 mA
10 mA
Load current, max
2.0 A
100 mA (high-speed operation)
1.0 A @ 30 °C
0.3 A @ 65 °C (standard operation)
1.0 A @ 30 °C
0.3 A @ 65 °C (standard operation)
Surge current, per point
Refer to Relay Contacts
Ratings on page 151
4.0 A every 1 s @ 30 °C; every 2 s @ 65 °C
(1)
Current, per common, max
5 A
2 A
4 A
Current, per controller, max
1440V A
2 A
4 A
Turn on time/
Turn off time, max
10 ms
2..5
μs
0.1 ms
1.0 ms
(1) Applies for general purpose operation only. Does not apply for high-speed operation.
Relay Contacts Ratings
Maximum Volts
Amperes
Amperes
Continuous
Volt-Amperes
Make
Break
Make
Break
120V AC
15 A
1.5 A
2.0 A
1800V A
180V A
240V AC
7.5 A
0.75 A
24V DC
1.0 A
1.0 A
28V A
125V DC
0.22 A
Environmental Specifications
Attribute
Value
Temperature, operating
IEC 60068-2-1 (Test Ad, Operating Cold),
IEC 60068-2-2 (Test Bd, Operating Dry Heat),
IEC 60068-2-14 (Test Nb, Operating Thermal Shock):
-20…65 °C (-4…149 °F)
Temperature, surrounding air,
max
65 °C (149 °F)
Temperature, non-operating
IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold),
IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat),
IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal
Shock):
-40…85 °C (-40…185 °F)
Relative humidity
IEC 60068-2-30 (Test Db, Unpackaged Damp Heat):
5…95% non-condensing
Vibration
IEC 60068-2-6 (Test Fc, Operating):
2 g @ 10…500 Hz