beautypg.com

Low preset (hscsts.lp), High preset output (hscsts.hpoutput), Low preset output (hscsts.lpoutput) – Rockwell Automation 2080-LC50 Micro830 and Micro850 Programmable Controllers User Manual User Manual

Page 150

background image

134

Rockwell Automation Publication 2080-UM002F-EN-E - December 2013

Chapter 8 Use the High-Speed Counter and Programmable Limit Switch

This is the latest high preset setting, which may be updated by PLS function from
the PLS data block.

Low Preset (HSCSTS.LP)

The HSCSTS.LP is the lower setpoint (in counts) that defines when the HSC
sub-system generates an interrupt.

The data loaded into the low preset must greater than or equal to the data
resident in the underflow (HSCAPP.UFSetting) parameter, or an HSC error is
generated. If the underflow and low preset values are negative numbers, the low
preset must be a number with a smaller absolute value.

This is the latest low preset setting, which may be updated by PLS function from
the PLS data block.

High Preset Output (HSCSTS.HPOutput)

The High Preset Output defines the state (1 = ON or 0 = OFF) of the outputs
on the controller when the high preset is reached. See Output Mask Bits
(HSCAPP.OutputMask) on page 126 for mo
re information on how to directly
turn outputs on or off based on the high preset being reached.

This is the latest high preset output setting, which may be updated by PLS
function from the PLS data block.

Low Preset Output (HSCSTS.LPOutput)

The Low Preset Output defines the state (1 = “on”, 0 = “off ”) of the outputs on
the controller when the low preset is reached. See Output Mask Bits
(HSCAPP.OutputMask) on page 126 for mo
re information on how to directly
turn outputs on or off based on the low preset being reached.

This is the latest low preset output setting, which may be updated by PLS
function from the PLS data block.

Description

Data Format

User Program Access

HSCSTS.LP

long word (32-bit INT)

read only

Description

Data Format

User Program Access

HSCSTS.HPOutput

long word (32-bit binary)

read only

Description

Data Format

User Program Access

HSCSTS.LPOutput

long word (32-bit binary))

read only

This manual is related to the following products: