Troubleshooting Appendix E

Error codes

This section lists possible error codes for your controller, as well as recommended
actions for recovery.

If an error persists after performing the recommended action, contact your local
Rockwell Automation technical support representative. For contact information,
go to

http://support.rockwellautomation.com/MySupport.asp

Indicator
Behavior

Probable Error

Probable Cause

Recommended Action

All indicators off

No input power or
power supply error

No line power

Verify proper line voltage and connections to the controller.

Power supply
overloaded

This problem can occur intermittently if power supply is overloaded when
output loading and temperature varies.

Power and FAULT
indicators on solid

Hardware faulted

Processor hardware
error

Cycle power. Contact your local Allen-Bradley representative if the error
persists.

Loose wiring

Verify connections to the controller.

Power on with
solid indicator and
FAULT indicator
flashing

Application fault

Hardware/software
major fault detected

For error codes and status information, refer to the Connected Components
Workbench online Help

Power on with
solid indicator and
FAULT indicator
flashing

Operating system fault

Firmware upgrade
unsuccessful

See

Flash Upgrade Your Micro800 Firmware on page 181

.