Rockwell Automation 2080-LC50 Micro830 and Micro850 Programmable Controllers User Manual User Manual
Page 186
170
Rockwell Automation Publication 2080-UM002F-EN-E - December 2013
Appendix A Specifications
Power consumption
33 W
Power supply voltage range
20.4…26.4V DC Class 2
I/O rating
Input 120V AC, 16 mA
Output 2 A, 240V AC,
2 A, 24V DC
Input 24V, 8.8 mA
Output 2 A, 240V AC, 2 A,
24V DC
Input 24V, 8.8 mA
Output 24V DC, 1 A per point (surrounding air
temperature 30 °C)
24V DC, 0.3 A per point (surrounding air temperature
65 °C)
Insulation stripping length
7 mm (0.28 in)
Enclosure type rating
Meets IP20
Pilot duty rating
C300, R150
–
Isolation voltage
250V (continuous), Reinforced
Insulation Type, Output to Aux
and Network, Inputs to
Outputs.
Type tested for 60 s @ 3250V
DC Output to Aux and
Network, Inputs to Outputs.
150V (continuous), Reinforced
Insulation Type, Input to Aux
and Network
Type tested for 60 s @ 1950V
DC Input to Aux and Network.
250V (continuous), Reinforced
Insulation Type, Output to Aux
and Network, Inputs to Outputs
Type tested for 60 s @ 3250V DC
Output to Aux and Network,
Inputs to Outputs
50V (continuous), Reinforced
Insulation Type, Input to Aux and
Network
Type tested for 60 s @ 720V DC,
Inputs to Aux and Network
50V (continuous), Reinforced Insulation Type, I/O to
Aux and Network, Inputs to Outputs
Type tested for 60 s @ 720V DC, I/O to Aux and
Network, Inputs to Outputs.
North American temp code
T4
(1) Use this Conductor Category information for planning conductor routing. Refer to Industrial Automation Wiring and Grounding Guidelines
Input Specifications
Attribute
2080-LC50-48AWB
2080-LC50-48QWB / 2080-LC50-48QVB / 2080-LC50-48QBB
120V AC Input
High-Speed DC Input
(Inputs 0…11)
Standard DC Input
(Inputs 12 and higher)
Number of Inputs
28
12
16
Input group to backplane
isolation
Verified by the following dielectric
tests: 1950V AC for 2 s
150V working voltage (IEC Class 2
reinforced insulation)
Verified by the following dielectric tests: 720V DC for 2 s
50V DC working voltage (IEC Class 2 reinforced insulation)
Voltage category
110V AC
24V DC sink/source
Operating voltage range
132V, 60Hz AC max
16.8…26.4V DC @ 65°C (149°F)
16.8…30.0V DC @ 30°C (86°F)
10…26.4V DC @ 65°C (149°F)
10…30.0V DC @ 30°C (86°F)
Off-state voltage, max
20V AC
5V DC
Off-state current, max
1.5 mA
1.5 mA
On-state current, min
5 mA @ 79V AC
5.0 mA @ 16.8V DC
1.8 mA @ 10V DC
On-state current, nom
12 mA @ 120V AC
7.6 mA @ 24V DC
6.15 mA @ 24V DC
On-state current, max
16 mA @ 132V AC
12.0 mA @ 30V DC
Nominal impedance
12 k
Ω @ 50 Hz
10 k
Ω @ 60 Hz
3 k
Ω
3.74 k
Ω
IEC input compatibility
Type 3
Inrush current, max
250 mA @ 120V AC
–
Input frequency, max
63 Hz
–
General Specifications – 2080-LC50-48AWB, 2080-LC50-48QWB, 2080-LC50-48QVB, 2080-LC50-48QBB
Attribute
2080-LC50-48AWB
2080-LC50-48QWB
2080-LC50-48QVB
2080-LC50-48QBB