Appendix E Troubleshooting
0xF021
The I/O configuration in the user program is
invalid or does not exist in the Micro800
controller.
Perform the following:
• Verify that you have selected the correct Micro800 controller from the Device
Toolbox.
• Correct the plug-in I/O module configuration in the user program to match
that of the actual hardware configuration.
• Recompile and reload the program.
• Put the Micro800 controller into Run mode.
• If the error persists, be sure to use Connected Components Workbench
programming software to develop and download the program.
0xF022
The user program in the memory module is
incompatible with the Micro800 controller’s
firmware revision.
Perform one of the following:
• Upgrade the Micro800 controller’s firmware revision using ControlFlash to be
compatible with the memory module.
• Replace the memory module.
• Contact your local Rockwell Automation technical support representative for
more information about firmware revisions for your Micro800 controller. For
more information on firmware revision compatibility, go to
0xF023
The controller program has been cleared. This
happened because:
• a power down occurred during program
download or transfer from the memory
module.
• the Flash Integrity Test failed (Micro810 only).
• Download or transfer the program.
0xF050
The embedded I/O configuration in the user
program is invalid.
Perform the following:
• Correct the embedded I/O configuration in the user program to match that of
the actual hardware configuration.
• Build and download the program using Connected Components Workbench.
• Put the Micro800 controller into Run mode.
• If the error persists, be sure to use Connected Components Workbench
programming software to develop and download the program.
0xF100
There is general configuration error detected in
the motion configuration downloaded from the
Connected Components Workbench software,
such as number of axis, or motion execution
interval being configured out of range.
Perform the following:
• Correct the axes configuration in the user program.
• If fault is consistent, upgrade to the latest software revision of Connected
Components Workbench.
See
Motion Axis Configuration in Connected Components Workbench on
0xF110
There is motion resource missing, such as
Motion_DIAG variable not defined.
Perform the following:
• Correct the axes configuration in the user program.
• If fault is consistent, upgrade to the latest Connected Components
Workbench software revision.
See
Motion Axis Configuration in Connected Components Workbench on
List of Error Codes for Micro800 controllers
Error Code
Description
Recommended Action