Publication 1757-IN500A-EN-P - September 2002
Operating System Installation Procedures 2-9
a. If necessary, adjust the Date and Time settings.
a. Set the appropriate Time Zone for your location.
b. Uncheck the Automatically adjust clock for daylight saving changes
option.
c. Click Next.
If setup has not found a suitable Network Device, you will be prompted
for installing one. Follow the instructions for adding a manufacturer
supplied driver or add the Microsoft Loop Back adapter.
15. Choose the Custom settings option and click Next.
16. At the Networking Components window, select Internet Protocol
(TCP/IP) and click Properties.
17. In the Networking Components Window,
a. Click the Use the following IP address option.
b. Enter the appropriate IP address information.
The following Private Networking IP Address scheme can be utilized
for the system to operate:
c. Enter the Subnet Mask 255.255.255.0.
d. Enter a default gateway if necessary.
ATTENTION
!
Failure to uncheck the Automatic adjustment for Daylight
Savings Time will cause Redundant Systems to loose
“Sync” when the time is automatically adjusted. Choosing
not to automatically adjust the time allows you to decide
when to make the adjustment (at a time that is not critical
to your process).
Table 2.A Private Networking IP Address scheme
Server Type
Suggested Private Networking IP Address
Non-Redundant Server or Primary
Redundant Server
NIC 1: 192.168.0.1
NIC 2: 192.168.1.1
NIC 3: 192.168.2.1
Backup Redundant Server
NIC 1: 192.168.0.2
NIC 2: 192.168.1.2
NIC 3: 192.168.2.2