I/o performance and capacity specifications, I/o performance and capacity specifications -21 – Rockwell Automation 1757-SWKIT5000 ProcessLogix R500.1 Installation and Upgrade Guide User Manual
Page 261
Publication 1757-IN500A-EN-P - September 2002
Performance and Capacity Specifications 11-21
I/O Performance and
Capacity Specifications
Every I/O device presents a load on the 1757-PLX52 system performance by
utilizing I/O network bandwidth and 1757-PLX52 memory and CPU
resources.
Many of these constraints are measured in I/O Units, which is a generic
loading definition used to normalize the load among the many different I/O
devices and families supported.
Refer to Table 11.R I/O Unit Load Constraints on page 11-21 for the I/O
unit load assigned to various devices and modules. By following these
configuration constraints, you can prevent the 1757-PLX52 from being
overloaded and increase the ability for the 1757-PLX52 to operate correctly..
Table 11.R I/O Unit Load Constraints
I/O Device or Module
I/O Units
1 1756/1757 chassis mounted I/O Module
1
1 1794 FLEX I/O or 1797 FLEX EX rail mounted I/O Module 1
1 1757-SIM FTA
4
1 1788-CN2FF, Foundation Fieldbus Linking Device
1
1 1757-FIM, Fieldbus Interface Module
3
1 DHRIO Module
1
1 SST-PFB-CLX Profibus Module
2 (for 64 Unit/CPM Limit)
6 (for 24 Unit/CNB Limit)
1 1756-DNB, DeviceNet Interface Module
1
Table 11.S I/O Module Capacity
I/O Module and Fieldbus Capacity
50 ms CEE
5 ms CEE
Maximum Number of I/O Units per 1757-PLX52
Refer to Table 11.R I/O Unit Load Constraints on page 11-21 for I/O unit definitions.
64
12
(local 1757/1756 I/O only)
Maximum Number of Remote I/O Chassis + 1757-FIM-Only Chassis+Remote Mixed
Chassis + 1794/1797-ACNR15s (combined) per 1757-PLX52.
8
0
(local 1757/1756 I/O only)
Maximum Number of I/O units per Downlink 1756-CNB
Refer to Table 11.R I/O Unit Load Constraints on page 11-21 for I/O unit definitions.
64 scheduled
24 unscheduled
0
(local 1757/1756 I/O only)
Maximum number of Downlink 1756-CNB’s per Controller Chassis
4
0
(local I/O only)
Maximum number of DHRIO modules per 1757-PLX52
2
2 (local chassis only)
Serial Interface Module: (TC-MUX021) related only
50ms CEE
5ms CEE
Maximum Number of Serial Interface Modules per 1757-PLX52
3
1
Maximum Number of FTA assemblies per Serial Interface Module (TC-MUX021)
• Each FTA connected counts as 4 I/O units in the 64 I/O units per 1757-PLX52 and
the 24 I/O units per 1756-CNB calculation above.
2
2
1788-CN2FF related only:
50ms CEE
5ms CEE