Firmware revision level reference, Firmware revision level reference -5 – Rockwell Automation 1757-SWKIT5000 ProcessLogix R500.1 Installation and Upgrade Guide User Manual
Page 185

Publication 1757-IN500A-EN-P - September 2002
Firmware Maintenance Procedures 7-5
Firmware Revision Level Reference
The following table lists the firmware revision levels for listed components
that are current for R500.1 along with the directory locations for firmware
upgrade files.
ATTENTION
!
This release of ProcessLogix supports only the firmware
versions listed in Table 7.A. When installing new systems
or repairing existing systems, you must ensure that all
modules meet the firmware version requirements listed in
Table 7.A.
Be certain that your process is off control before you begin
any upgrade procedure. This means the 1757-PLX52
should be in the Idle state.
Table 7.A Hardware component firmware revision level reference for R500.1
Component
Name
Model Number
Revision
Level for
R500.1
Directory
File
Process Controller
Module
1757-PLX52
(redundant-
compliant)
AV 500.1-01.1
BV 500.1-01.1
C:\Honeywell\tps50\system\bin
Cee5.pcm
Cee50.pcm
Cpmboot.pcm
Serial Interface
Module (SIM)
TC-MUX021
AV 500.1-01.1
BV 500.1-01.1
C:\Honeywell\tps50\system\bin
Simboot.pcm
simrex.pcm
Use this base directory path to locate the firmware directories and files for the following modules:
C:\Honeywell\tps50\system\firmware
Redundancy
Module (RM)
1757-SRM
AV 2.15
BV 2.13
\1757-SRM\2_15
99450204.nvs
ControlNet Bridge
module (CNB)
1756-CNB/B
(single media)
1756-CNBR/B
(dual media)
2.27
cnb\1756-CNB(R)-B\2_27
99422005.nvs
1756-CNB/C
(single media)
1756-CNBR/C
(dual media)
4.24
cnb\1756-CNB(R)-C\4_24
99404317.nvs
1756-CNB/D
(single media)
1756-CNBR/D
(dual media)
5.31
cnb\1756-CNB(R)-D\5_31
99415517.nvs
FLEX Ex ControlNet
Adapter
1797-ACNR15
(redundant media)
3.5
\1797-ACN(R)15\3_5
99423302.nvs