Rockwell Automation 1757-SWKIT5000 ProcessLogix R500.1 Installation and Upgrade Guide User Manual
Page 224
![background image](/manuals/579176/224/background.png)
Publication 1757-IN500A-EN-P - September 2002
8-26 Supplementary Procedures
11. Click Operate
⇒
Inactivate
⇒
This CEE’s SCMs to inactivate all
assigned SCMs, if applicable.
12. Click Yes in the dialog box to confirm the action.
13. Click Operate
⇒
Inactivate
⇒
This CEE and its IOMs and CMs to
inactivate the CEE and all assigned IOMs and CMs.
14. Click Yes in the dialog box to confirm the action.
Color of all icons changes to Blue.
15. Select the contents (CMs, SCMs, IOMs) of the CEE folder and click
Edit
⇒
Delete.
16. Click Delete Selected object(s) to delete the selected objects.
17. Click the CPM icon, and click Edit
⇒
Delete.
18. Click Delete Selected object(s) to delete the non-redundant CPM.
19. In Project tab, click the CEE folder icon.
20. Click Tools
⇒
Assign to call up the Controller Assignments dialog
box.
21. Confirm that the check boxes for the selection Show CMs and Show
IOMs are checked.
22. Select the CEE associated with the non-redundant CPM in the Select a
CEE list box.
23. Select all the modules listed in the Assigned Modules list box.
Document the modules you will be unassigning.
24. Click Unassign.
25. Wait for modules to be unassigned and removed from the Assigned
Modules list box.
26. Click Close and return to the Project tab.
27. Click the CPM icon and click Edit
⇒
Delete.
28. Click the Delete Selected object(s) button to delete the CPM and its
associated CEE.
29. Close Control Builder.