Disabling erdb replication, Exporting the database using control builder – Rockwell Automation 1757-SWKIT5000 ProcessLogix R500.1 Installation and Upgrade Guide User Manual
Page 103
![background image](/manuals/579176/103/background.png)
Publication 1757-IN500A-EN-P - September 2002
ProcessLogix Server Upgrade Procedures 4-15
Disabling ERDB Replication
This procedure is only required for a Redundant Server Pair. Perform these
steps on SERVERB only. If you have a non-redundant server, skip to
Exporting the Database Using Control Builder on page 4-15.
1. Logon to the SERVERB as ps_user.
2. Click Start
⇒
Programs
⇒
ProcessLogix Engineering Tools
⇒
DB Admin.
3. Click the
+
sign to expand DbAdmin.
4. In the Login dialog box make these entries:
a. Enter >mngr< as the default User Name.
b. Enter >mngr1< as the default Password.
c. Enter >localhost< in the Server Name field.
5. Click the
+
sign to expand ProcessLogix Node.
6. Click Admin Tasks.
7. Click Disable Replication.
8. Click OK at the Disabled Database Replication prompt.
9. Close DbAdmin.
Exporting the Database Using Control Builder
Perform these steps on a non-redundant Server or SERVERB.
1. Using Windows Explorer, create the folder C:\Data\ExportDB.
2. Click Start
⇒
Programs
⇒
ProcessLogix Engineering Tools
⇒
Control Builder.
3. In the Login dialog box, make these entries:
a. Enter >mngr< as the default User Name.
b. Enter >mngr1< as the default Password.
c. Enter >localhost< in the Server Name field.
4. Click OK.
5. Click File
⇒
Export.