PowerMonitor 1000 Data Tables Appendix A

Table 40 - Write Error Status Results Parameters

CSP File No.

N27

CIP Instance

20

Applies to

All Models

No. of Elements

3

No. of Words

3

Data Type

Integer

Data Access

Read

Table 41 - Write Error Status Results

Element

No.

Modbus

Address

Element Name

Range

Description

0

30801

Table Number or Instance

All Write Enabled Tables

Indicates the last table that was written.

1

30802

Offending Element

Length of current table - 1

If the most recent write was successful this returns a

(-1). If the write was unsuccessful this is the first

rejected element in the table write.

2

30803

Terminal Lock On

0…1

If a write was made to a table that has elements that

are locked this value is 1.