beautypg.com

Rockwell Automation 1408-EMxx PowerMonitor 1000 Unit User Manual

Page 82

background image

82

Rockwell Automation Publication 1408-UM001D-EN-P - September 2013

Appendix A PowerMonitor 1000 Data Tables

9

40510

Load Factor log

Auto Log Setting

31

0…31

Automatically stores the current peak,

average, and load factor results as a record

in the non-volatile load factor log and resets

the log at the specified day of the month.
0 = Disables the auto clear feature.

1 = Store and clear the table on the 1st day of

each month.

2 = 2nd Day

3 = 3rd day

29…31 = Store and clear table at the last

day of the month.

10

40511

Reserved

0

0

Reserved for future use.

11

40512

Reserved

0

0

Reserved for future use.

Table 16 - Log Configuration

Element

No.

Modbus

Address

Element Name

Default

Value

Range

TR1

TR2

EM

1

EM

2

EM

3

Description

Table 17 - Command Table Parameters

CSP File No.

F16

CIP Instance

9

No. of Elements

22

No. of Words

44

Data Type

Float

Data Access

Write

This manual is related to the following products: