beautypg.com

Rockwell Automation 1408-EMxx PowerMonitor 1000 Unit User Manual

Page 104

background image

104

Rockwell Automation Publication 1408-UM001D-EN-P - September 2013

Appendix A PowerMonitor 1000 Data Tables

Table 47 - Load Factor Log Results Parameters

CSP File No.

F30

CIP Instance

23

No. of Elements

14

No. of Words

28

Data Type

Float

Data Access

Read

Table 48 - Load Factor Log Results

Element

No.

Modbus

Address

Element Name

Range

TR1

TR2

EM1

EM2

EM3

Description

0

31101-2

Record Number

1…13

The record number of this data.

1

31103-4

End Date yy/mm/dd

-

The date that this record was stored.

2

31105-6

Elapsed Time

0.000…

9,999,999

Amount of time (in hours) that has elapsed

since the last clear of the peak and average

values. Updated at the end of each demand

interval.

3

31107-8

Peak Demand

kWatts

+/-

0.000…9,999,99

9

The largest magnitude demand for kwatts

that occurred over all of the demand

intervals since the last clear command or

auto-clear day.

4

31109-10

Average Demand

kWatts

+/-

0.000…9,999,99

9

A running average of demand for kwatts

from the end of each demand period since

the last clear command or auto-clear day.

5

31111-12

Load Factor kWatts

0…100%

Average Demand kW / Peak Demand kW.

This is a demand management metric that

indicates how ‘spiky’ (or ‘level’) a load is

over a period of time (usually 1 month). A

value approaching 100% indicates a

constant load.

6

31113-14

Peak Demand kVAR

+/- 0.000…

9,999,999

The largest magnitude demand for kVAR

that occurred over all of the demand

intervals since the last clear command or

auto-clear day.

7

31115-16

Average Demand

kVAR

+/- 0.000…

9,999,999

A running average of demand for kVAR from

the end of each demand period since the

last clear command or auto-clear day.

8

31117-18

Load Factor kVAR

0…100%

Average Demand kVAR / Peak Demand

kVAR. This is a demand management metric

that indicates how ‘spiky’ (or ‘level’) a load

is over a period of time (usually 1 month). A

value approaching 100% indicates a

constant load.

This manual is related to the following products: