Appendix A PowerMonitor 1000 Data Tables
Table 47 - Load Factor Log Results Parameters
CSP File No.
F30
CIP Instance
23
No. of Elements
14
No. of Words
28
Data Type
Float
Data Access
Read
Table 48 - Load Factor Log Results
Element
No.
Modbus
Address
Element Name
Range
TR1
TR2
EM1
EM2
EM3
Description
0
31101-2
Record Number
1…13
•
•
The record number of this data.
1
31103-4
End Date yy/mm/dd
-
•
•
The date that this record was stored.
2
31105-6
Elapsed Time
0.000…
9,999,999
•
•
Amount of time (in hours) that has elapsed
since the last clear of the peak and average
values. Updated at the end of each demand
interval.
3
31107-8
Peak Demand
kWatts
+/-
0.000…9,999,99
9
•
•
The largest magnitude demand for kwatts
that occurred over all of the demand
intervals since the last clear command or
auto-clear day.
4
31109-10
Average Demand
kWatts
+/-
0.000…9,999,99
9
•
•
A running average of demand for kwatts
from the end of each demand period since
the last clear command or auto-clear day.
5
31111-12
Load Factor kWatts
0…100%
•
•
Average Demand kW / Peak Demand kW.
This is a demand management metric that
indicates how ‘spiky’ (or ‘level’) a load is
over a period of time (usually 1 month). A
value approaching 100% indicates a
constant load.
6
31113-14
Peak Demand kVAR
+/- 0.000…
9,999,999
•
•
The largest magnitude demand for kVAR
that occurred over all of the demand
intervals since the last clear command or
auto-clear day.
7
31115-16
Average Demand
kVAR
+/- 0.000…
9,999,999
•
•
A running average of demand for kVAR from
the end of each demand period since the
last clear command or auto-clear day.
8
31117-18
Load Factor kVAR
0…100%
•
•
Average Demand kVAR / Peak Demand
kVAR. This is a demand management metric
that indicates how ‘spiky’ (or ‘level’) a load
is over a period of time (usually 1 month). A
value approaching 100% indicates a
constant load.