Rockwell Automation 1408-EMxx PowerMonitor 1000 Unit User Manual
Page 80
80
Rockwell Automation Publication 1408-UM001D-EN-P - September 2013
Appendix A PowerMonitor 1000 Data Tables
Table 15 - Log Configuration Parameters
CSP File No.
N15
CIP Instance
8
No. of Elements
12
No. of Words
12
Data Type
Integer
Data Access
Read/Write
Table 16 - Log Configuration
Element
No.
Modbus
Address
Element Name
Default
Value
Range
TR1
TR2
EM1
EM2
EM3
Description
0
40501
Password
0
0…
9999
•
•
•
When writing the complete table this
parameter allows the input data to be
accepted. When writing a single parameter
the separate password table should be used.
Returns -1 on a read.
1
40502
Energy Log
Interval
15 min
-1…60
•
•
•
Selects how often a record is logged
(minutes). A value of 0 disables periodic
logging of records. A value of –1 causes
logging of records to be synchronized to the
end of the demand interval.
2
40503
Energy Log Mode
1
0…1
•
•
•
This parameter set the action of the log once
is has filled to capacity. Setting the option to
0 allows the log to fill but stops at the end.
Option 1 lets the log fill and then oldest
records are deleted and replaced with new
records.
0 = Fill and Stop
1 = Overwrite, When the log is filled new
records replace the oldest records.
3
40504
Time of Use Log
Auto Log Setting
31
0…31
•
•
•
Automatically stores the current record for
the month replacing the oldest record if the
log is full. The log holds 12 months plus the
current record.
0 = Disables the auto clear feature.
1 = Store and clear the table on the 1st day of
each month.
2 = 2nd Day
3 = 3rd day
…
29…31 = Store and clear table at the last
day of the month.