Rockwell Automation 1408-EMxx PowerMonitor 1000 Unit User Manual

Page 80

background image

80

Rockwell Automation Publication 1408-UM001D-EN-P - September 2013

Appendix A PowerMonitor 1000 Data Tables

Table 15 - Log Configuration Parameters

CSP File No.

N15

CIP Instance

8

No. of Elements

12

No. of Words

12

Data Type

Integer

Data Access

Read/Write

Table 16 - Log Configuration

Element

No.

Modbus

Address

Element Name

Default

Value

Range

TR1

TR2

EM1

EM2

EM3

Description

0

40501

Password

0

0…

9999

When writing the complete table this

parameter allows the input data to be

accepted. When writing a single parameter

the separate password table should be used.

Returns -1 on a read.

1

40502

Energy Log

Interval

15 min

-1…60

Selects how often a record is logged

(minutes). A value of 0 disables periodic

logging of records. A value of –1 causes

logging of records to be synchronized to the

end of the demand interval.

2

40503

Energy Log Mode

1

0…1

This parameter set the action of the log once

is has filled to capacity. Setting the option to

0 allows the log to fill but stops at the end.

Option 1 lets the log fill and then oldest

records are deleted and replaced with new

records.
0 = Fill and Stop

1 = Overwrite, When the log is filled new

records replace the oldest records.

3

40504

Time of Use Log

Auto Log Setting

31

0…31

Automatically stores the current record for

the month replacing the oldest record if the

log is full. The log holds 12 months plus the

current record.
0 = Disables the auto clear feature.

1 = Store and clear the table on the 1st day of

each month.

2 = 2nd Day

3 = 3rd day

29…31 = Store and clear table at the last

day of the month.