Rockwell Automation 1408-EMxx PowerMonitor 1000 Unit User Manual
Page 73
Rockwell Automation Publication 1408-UM001D-EN-P - September 2013
73
PowerMonitor 1000 Data Tables Appendix A
15
40131-32
Demand
Period Length
15 min
0…99
•
•
Specifies the desired period for demand
calculations. When set to 0 there are no
projected demand calculations. If the internal
timer is selected a setting of 0 turns the
demand function off.
16
40133-34
Number of
Demand
Periods
1
1…15
•
•
Specifies the number of demand periods to
average for demand measurement.
17
40135-36
Forced
Demand Sync
Delay
10 s
0…900 s
•
•
When the power monitor is configured for
external demand control the unit delays for xxx
seconds after the expected control pulse has
not been received. The demand period starts
over and a record is recorded in the status log.
0 = Wait forever
1…900 = Wait this many seconds before
starting a new demand period.
This setting becomes active when the demand
interval is set from -1…-99 minutes.
18
40137-38
Unit Error
Action
1
0…1
•
•
•
•
•
This parameter determines the action when a
unit error occurs.
0 = Halt on error and make status LED solid red
1 = Reset power monitor hardware.
19
40139-40
Software Error
Log Full Action
1
0…1
•
•
•
•
•
This parameter determines the action when a
firmware failure is detected and the error log is
full.
0 = Halt on error and wait for clear log
command, also make status LED solid red
1 = Perform a firmware reset.
20
40141-42
Reserved
0
0
•
•
•
•
•
Reserved for future use.
21
40143-44
Reserved
0
0
•
•
•
•
•
Reserved for future use.
Table 7 - Advanced Configuration
Element
No.
Modbus
Address
Range
Element
Name
Default
Value
Range
TR
1
TR
2
EM
1
EM
2
EM
3
Description