PowerMonitor 1000 Unit Features Chapter 2
Miscellaneous Functions
The power monitor includes a small number of miscellaneous functions that you
can select. Set-up parameters of these functions are in the Advanced
Configuration set-up menu.
Commands
The power monitor offers the following commands. The power monitor
Commands table can be accessed using the LCD screen, the HyperTerminal
communication tool, the Web interface, or via communication.
Commands that do not apply to the power monitor model are ignored.
Parameter
Description
Range
Default
User
Setting
New
Password
Select a new password if desired to help
prevent unauthorized changes to the unit
setup.
0…9999 0
Metering
Result
Averaging
If enabled, metering results are averaged by
using the previous eight cycles to smooth
the results.
0 = Off
1 = On
1
Log Status
Input
Changes
(1)
(1) Log status input changes parameter is not accessible from the LCD screen.
If disabled, prevents routine status input
changes from filling up the status log.
Useful when a status input is used for pulse
counting or demand EOI synch.
0 =
Disable
1 =
Enable
0
Unit Error
Action
Determines the unit’s response to a
hardware or firmware error.
0 = Halt, make status indicator solid red
1 = Reset the unit
0…1
1
Software
Error Log Full
Action
Determines the unit response when a
firmware failure is detected and the error
log is full.
0 = Halt on error and wait for clear log
command, make status indicator solid red
1 = Perform a firmware reset
0…1
1
Command
Parameters
Action
Set kWh register
GWh / kWh forward
GWh / kWh reverse
Presets forward and reverse
energy values, resets if
parameters = 0
Set kVARh register
GVARh / kVARh forward
GVARh / kVARh reverse
Set kVAh register
GVAh / kVAh forward
GVAh / kVAh reverse
Clear all energy registers
-
Resets all energy values
Set Status 1 count
New status 1 count
Presets or resets status input
count
Set Status 2 count
New status 2 count
Clear energy log
-
Clears all data from energy log
Force KYZ output on
-
Forces the KYZ output state,
over-rides automatic action
Force KYZ output off
-
Remove force from KYZ
-
Restores automatic action of
KYZ output as configured
Restore factory defaults
-
Clears all user-configured
values from the setup menus to
their factory default settings