Results, Related functions, Voltage, current, and frequency metering – Rockwell Automation 1408-EMxx PowerMonitor 1000 Unit User Manual
Page 36: Metered parameters, Setup
![background image](/manuals/579043/36/background.png)
36
Rockwell Automation Publication 1408-UM001D-EN-P - September 2013
Chapter 2 PowerMonitor 1000 Unit Features
Results
Power metering results may be viewed using the following methods:
•
Web interface
•
LCD screen
•
Communication
•
HyperTerminal communication tool
Related Functions
•
Metering result averaging
•
Configuration lock
Voltage, Current, and
Frequency Metering
This function applies to catalog numbers 1408-TR1, 1408-TR2, and 1408-EM3.
Metered Parameters
The power monitor calculates and returns voltage, current, and frequency
measurements including these:
•
L1, L2, L3, and Average Current, A
•
L1-N, L2-N, L3-N, and Average L-N Voltage, V
•
L1-L2, L2-L3, L3-L1, and Average L-L Voltage, V
•
Frequency
•
Percent Current Unbalance
•
Percent Voltage Unbalance
Line-to-neutral voltage results are not provided for Delta and Open Delta wiring
modes.
Voltage and current unbalance are calculated according to the following formula.
Setup
Only basic analog-input setup is required for power metering.
Maximum Deviation from Average 100
Average
----------------------------------------------------------------------------------------------------------