Rockwell Automation 1408-EMxx PowerMonitor 1000 Unit User Manual
Page 85

Rockwell Automation Publication 1408-UM001D-EN-P - September 2013
85
PowerMonitor 1000 Data Tables Appendix A
Table 19 - Log Request Table Parameters
CSP File No.
N17
CIP Instance
10
No. of Elements
11
No. of Words
11
Data Type
Integer
Data Access
Read/Write
Table 20 - Log Request Table
Element
No.
Modbus
Address
Element Name
Default
Value
Range
TR1
TR2
EM1
EM2
EM3
Description
0
40701
Selected Log
0
0…5
•
•
•
•
•
Selects the log that information is returned
from. Once a single request has been
made the auto return feature will bring
back successive records each time the log
is read. Some logs support individual
record requests.
1 = Unit Status Log
2 = Min/Max Log
3 = Energy Log
4 = Load Factor Log
5 = Time of Use Log kWh
6 = Time of Use Log kVAR
7 = Time of Use Log kVA
If your catalog number does not support
the requested log item the power monitor
will ignore the request.
1
40702
Chronology of
Auto Return Data
1
0…1
•
•
•
•
•
The date chronology of the returned
records.
0 = Reverse direction
1 = Forward direction
2
40703
The Min/Max
record to be
returned
0
0…35
0…31
0…15
•
•
•
Selects the Min/Max record number to be
returned. See the table for Min/Max
record list.
0 = Use incremental return and the
chronology selected.
EM3 = 1…35
TR2 = 1…31
TR1 = 1…15
3
40704
Number of Unit
Status Records
-
1…50
•
•
•
•
•
On a read of this table the value of this
parameter is the number of Unit Status
Records available. This log is only returned
using the incremental return method.
4
40705
Number of Energy
Log Records
-
0…
17,280
•
•
•
On a read of this table the value of this
parameter is the number of Energy Log
Records available.