Rockwell Automation 1408-EMxx PowerMonitor 1000 Unit User Manual
Page 57
![background image](/manuals/579043/57/background.png)
Rockwell Automation Publication 1408-UM001D-EN-P - September 2013
57
Explicit Messaging Chapter 5
Follow these steps to configure a message.
1. Choose the appropriate parameters in the Message Configuration window.
Parameter
Choice
Message Type
Choose message type CIP Generic.
Service Type
Read: Select service type Get Attribute Single
Write: Select service type Set Attribute Single
Instance
for the CIP Instance of the data table you are requesting to
read. In this example, the power monitor’s Voltage, Amp, and Frequency data
table is instance 14.
Class
4
Attribute
3
Destination
Get Attribute Single - This is the controller tag in which to store the data being
read.
Source Element
Set Attribute Single - Refer to
for the address of the specific data
table address you’re writing to.
Source Length
Set Attribute Single - This is the number of elements of the source element, to
be written to the power monitor.