beautypg.com

Data table access, Data table data format – Rockwell Automation 1408-EMxx PowerMonitor 1000 Unit User Manual

Page 50

background image

50

Rockwell Automation Publication 1408-UM001D-EN-P - September 2013

Chapter 3 PowerMonitor 1000 Memory Organization

Data Table Access

Controllers and client applications may read or write single element, multiple

elements or complete tables as permitted by the addressing selected.

Each data table’s read/write access is listed in

Appendix A

.

The power monitor requires a valid password before it accepts a write. There are

two ways a password may be written.

An entire table including a valid password may be written.

A valid password may be written to the Single element password write

table which then enables single element writes until 30 minutes without a

single element write elapses.

Data Table Data Format

The power monitor stores data in two basic formats.

Integer, in which the 16-bit word may be represented by a signed integer

value or a bit field

Floating-point, in the 32-bit IEEE 754 format

Modbus input registers and holding registers are 16 bits long. Floating point

values in the data tables are represented as big-Endian two-register arrays in

IEEE-754 floating point format. The Modbus client application must be able to

reassemble the two-word array into a valid floating-point value.

An example Modbus address for a floating-point value is 40101-2. Register

40101 holds the most significant bytes of the number and 40102 holds the lowest

significant bytes.

This manual is related to the following products: