Rockwell Automation 1408-EMxx PowerMonitor 1000 Unit User Manual
Page 76
76
Rockwell Automation Publication 1408-UM001D-EN-P - September 2013
Appendix A PowerMonitor 1000 Data Tables
13
40314
SNTP Mode Select
0
0…2
•
•
•
•
•
This mode selects the mode of the SNTP
function or to disable the SNTP function.
0 = Disable
1 = Unicast - The SNTP address points to a
unicast server.
2 = Anycast Mode - The SNTP address is a
broadcast address of an anycast group.
14
40315
SNTP Update Interval
300
1…32766
•
•
•
•
•
Indicates how often the time is updated from
the SNTP Server. The unit is minute.
15
40316
Time Zone Select
7
0…32
•
•
•
•
•
The time zone table has detailed time zone
information.
16
40317
Time Server IP
Address Byte a
0
0…255
•
•
•
•
•
The internal clock is set after each Time set
interval has expired. The Time server IP
address is the SNTP time server where the
request is handled.
17
40318
Time Server IP
Address Byte b
0
0…255
•
•
•
•
•
The internal clock is set after each Time set
interval has expired. The Time server IP
address is the SNTP time server where the
request is handled.
18
40319
Time Server IP
Address Byte c
0
0…255
•
•
•
•
•
The internal clock is set after each Time set
interval has expired. The Time server IP
address is the SNTP time server where the
request is handled.
19
40320
Time Server IP
Address Byte d
0
0…255
•
•
•
•
•
The internal clock is set after each Time set
interval has expired. The Time server IP
address is the SNTP time server where the
request is handled.
20
40321
Demand Broadcast
Master Select
0
0…1
•
•
When configured as a Master the power
monitor broadcasts an end of demand
interval broadcast to the UDP port number
configured.
0 = Slave
1 = Master control
21
40322
Broadcast Port
Number
300
300…400
•
•
When configured as a Master and External
Demand Source or Ethernet Demand
Broadcast the port number is the listening or
broadcast port for the UDP message.
22
40323
Reserved
0
0
•
•
•
•
•
Reserved for future use.
Table 11 - Ethernet Configuration
Element
No.
Modbus
Address
Element Name
Default
Value
Range
TR
1
TR
2
EM
1
EM
2
EM
3
Description