PowerMonitor 1000 Unit Features Chapter 2

Commands

Clear single min/max log record

Clear min/max log

Related Functions

Energy metering

Demand metering

Voltage, current and frequency metering

Power metering

Load Factor Log

The power monitor maintains a 12-month record of demand and load factor.

Load factor is average demand divided by peak demand and is a measure of load

variability.

This function applies to catalog numbers 1408-EM2 and 1408-EM3.

Logged Parameters

The load factor log consists of 13 records, an in-process record for the current

month, and one record for the previous 12 months. The monthly records operate

in a circular or FIFO fashion. On a user-selected day each month, the current

record is pushed into the monthly record stack and cleared. Each record contains

the following data:

Real power demand, peak and average, kW

Real power load factor, percent

Reactive power demand, peak and average, kVAR

Reactive power load factor in percent

Apparent power demand, peak and average, kVA

Apparent power load factor in percent

Results

Load factor log records can be accessed only via communication.

Commands

Store and clear current Load Factor Record

Clear Load Factor Log