Configure df1 full-duplex – Rockwell Automation 1408-EMxx PowerMonitor 1000 Unit User Manual
Page 116
116
Rockwell Automation Publication 1408-UM001D-EN-P - September 2013
Appendix B SCADA Applications
Configure DF1 Full-duplex
You need to use a RS232 to RS485 converter, like the 1761-NET-AIC or B&B
Electronics Converter – Model 485SD9TB.
1. Create a RS232 DF1 devices driver in RSLinx software.
2. Perform an Auto-configure.
3. Verify connections if Auto-configure fails.
4. Perform an RSWho to verify that RSLinx software is communicating to
the power monitor.
RSLinx software driver configuration is complete.
Configure RSLinx Software Driver Configuration for DH485
You need to use an RS232 to RS485 converter like the 1761-NET-AIC converter
or B&B Electronics Converter - Model 485SD9TB.
1. Open the RSLinx Launch Control Panel.
2. Start RSLinx software to run as normal application, not as service.
3. Create a 1747-PIC/AIC+ Driver in RSLinx software.
4. Verify that the communication rate is the same as the communication rate
set for your power monitor.
5. Set the node address and maximum node address of RSLinx Driver.
6. Perform an RSWho to verify that RSLinx software is communicating to
the power monitor.
7. Restart RSLinx software to run as service.