Rockwell Automation 1408-EMxx PowerMonitor 1000 Unit User Manual

Page 101

background image

Rockwell Automation Publication 1408-UM001D-EN-P - September 2013

101

PowerMonitor 1000 Data Tables Appendix A

9

30910

Flash Memory

0…511

0 indicates normal operation. Status bits are

Bit 0 = Overall status

Bit 1 = Boot code checksum

Bit 2 = Application code checksum

Bit 3 = Calibration data CRC

Bit 4 = No calibration data

Bit 5 = Wrong application FRN

Bit 6 = Invalid model type

Bit 7 = WIN mismatch

Bit 8 = missing upgrade block

10

30911

SRAM

0…1

0 indicates normal operation.

Bit 0 = Read/write test

11

30912

NVRAM

0…1

0 indicates normal operation.

Bit 0 = Read/write test

12

30913

SPI Interface

0…1

0 indicates normal operation.

Bit 0 = SPI device not responding

13

30914

Real Time Clock

0…3

0 indicates normal operation.

Bit 0 = RTC status

Bit 1 = Time Zone Set Failed

14

30915

Watchdog Timer

0…1

0 indicates normal operation.

Bit 0 = Watchdog time out

15

30916

Metering

0…1

0 indicates normal operation.

Bit 0 = Metering status

16

30917

LCD Interface

0…1

0 indicates normal operation.

Bit 0 = LCD Interface status

17

30918

Serial Communications

0…1

0 indicates normal operation.

Bit 0 = Serial Interface status

18

30919

Ethernet Communications

0…511

0 indicates normal operation.

Bit 0 = Ethernet Communications status

Bit 1 = SNTP Server timeout status

Bit 2 = Duplicate IP Address status

Bit 3 = Invalid IP/Netmask address

Bit 4 = Invalid gateway address

Bit 5 = Invalid SNTP time server address

Bit 6 = Modbus stack run status

Bit 7 = Demand broadcast thread run status

Bit 8 = SNTP thread run status

19

30920

Input Over Range

0…3

0 indicates normal operation.

Bit 0 = Voltage Input over range

Bit 1 = Current Input over range

20

30921

Phase Loss Detection

0…7

0 Indicates normal running condition.

Bit 0 = Loss of phase A

Bit 1 = Loss of phase B

Bit 2 = Loss of phase C

21

30922

Configuration Locked

0…1

Reports 1 if configuration lock is applied.

22

30923

Password Accepted

0…1

1 indicates the password is verified and active

23

30924

Error Recorded

0

Is incremented by 1 when an internal error happens

24

30925

Troubleshooting Times

Remaining

0…30

Remaining times for troubleshooting mode.

Table 43 - Unit Run Status Results

Element

No.

Modbus

Address

Element Name

Range

Description