Rockwell Automation 1408-EMxx PowerMonitor 1000 Unit User Manual
Page 101
Rockwell Automation Publication 1408-UM001D-EN-P - September 2013
101
PowerMonitor 1000 Data Tables Appendix A
9
30910
Flash Memory
0…511
0 indicates normal operation. Status bits are
Bit 0 = Overall status
Bit 1 = Boot code checksum
Bit 2 = Application code checksum
Bit 3 = Calibration data CRC
Bit 4 = No calibration data
Bit 5 = Wrong application FRN
Bit 6 = Invalid model type
Bit 7 = WIN mismatch
Bit 8 = missing upgrade block
10
30911
SRAM
0…1
0 indicates normal operation.
Bit 0 = Read/write test
11
30912
NVRAM
0…1
0 indicates normal operation.
Bit 0 = Read/write test
12
30913
SPI Interface
0…1
0 indicates normal operation.
Bit 0 = SPI device not responding
13
30914
Real Time Clock
0…3
0 indicates normal operation.
Bit 0 = RTC status
Bit 1 = Time Zone Set Failed
14
30915
Watchdog Timer
0…1
0 indicates normal operation.
Bit 0 = Watchdog time out
15
30916
Metering
0…1
0 indicates normal operation.
Bit 0 = Metering status
16
30917
LCD Interface
0…1
0 indicates normal operation.
Bit 0 = LCD Interface status
17
30918
Serial Communications
0…1
0 indicates normal operation.
Bit 0 = Serial Interface status
18
30919
Ethernet Communications
0…511
0 indicates normal operation.
Bit 0 = Ethernet Communications status
Bit 1 = SNTP Server timeout status
Bit 2 = Duplicate IP Address status
Bit 3 = Invalid IP/Netmask address
Bit 4 = Invalid gateway address
Bit 5 = Invalid SNTP time server address
Bit 6 = Modbus stack run status
Bit 7 = Demand broadcast thread run status
Bit 8 = SNTP thread run status
19
30920
Input Over Range
0…3
0 indicates normal operation.
Bit 0 = Voltage Input over range
Bit 1 = Current Input over range
20
30921
Phase Loss Detection
0…7
0 Indicates normal running condition.
Bit 0 = Loss of phase A
Bit 1 = Loss of phase B
Bit 2 = Loss of phase C
21
30922
Configuration Locked
0…1
Reports 1 if configuration lock is applied.
22
30923
Password Accepted
0…1
1 indicates the password is verified and active
23
30924
Error Recorded
0
Is incremented by 1 when an internal error happens
24
30925
Troubleshooting Times
Remaining
0…30
Remaining times for troubleshooting mode.
Table 43 - Unit Run Status Results
Element
No.
Modbus
Address
Element Name
Range
Description