beautypg.com

Rockwell Automation 1408-EMxx PowerMonitor 1000 Unit User Manual

Page 93

background image

Rockwell Automation Publication 1408-UM001D-EN-P - September 2013

93

PowerMonitor 1000 Data Tables Appendix A

Table 31 - Energy Results Parameters

CSP File No.

F23

CIP Instance

16

No. of Elements

19

No. of Words

38

Data Type

Float

Data Access

Read

Table 32 - Energy Results

Element

No.

Modbus

Address

Element Name

Range

TR1

TR2

EM1

EM2

EM3

Description

0

30401-2

Status 1 Count xM

0…9,999,999

Status 1 Count times 1,000,000

1

30403-4

Status 1 Count x1

0…999,999

Status 1 count times 1

2

30405-6

Status 2 Count xM

0…9,999,999

Status 2 Count times 1,000,000

3

30407-8

Status 2 Count x1

0…999,999

Status 2 count times 1

4

30409-10

GWh Fwd

0…9,999,999

Forward gigawatt hours

5

30411-12

kWatth Fwd

0.000…999,999

Forward kilowatt hours

6

30413-14

GWh Rev.

0…9,999,999

Reverse gigawatt hours

7

30415-16

kWatth Rev.

0.000…999.999

Reverse kilowatt hours

8

30417-18

GWh Net

+/- 0…9,999,999

Net gigawatt hours

9

30419-20

kWatth Net

+/- 0.000…999,999

Net kilowatt hours

10

30421-22

GVARH Fwd

0…9,999,999

Forward gigaVAR hours

11

30423-24

kVARh Fwd

0.000…999,999

Forward kiloVAR hours

12

30425-26

GVARH Rev.

0…9,999,999

Reverse gigaVAR hours

13

30427-28

kVARh Rev.

0.000…999,999

Reverse kiloVAR hours

14

30429-30

GVARH Net

+/- 0…9,999,999

Net gigaVAR hours

15

30431-32

kVARh Net

+/- 0.000…999,999

Net kiloVAR hours

16

30433-34

GVAh Net

0…9,999,999

Net gigaVA hours

17

30435-36

kVAh

0.000…999,999

Net kiloVA hours

18

30437-38

Metering Iteration

0…9,999,999

Increments by 1 for each new

metering calculation.

This manual is related to the following products: