2 - powermonitor 1000 unit features, Analog input setup, Setup – Rockwell Automation 1408-EMxx PowerMonitor 1000 Unit User Manual
Page 25: Related functions, Chapter 2, Powermonitor 1000 unit, Features, Powermonitor 1000 unit features, Chapter

Rockwell Automation Publication 1408-UM001D-EN-P - September 2013
25
Chapter
2
PowerMonitor 1000 Unit Features
This section describes in detail the functions of the power monitor. Each
function includes information on set-up menus and parameters used to control its
operation.
Analog Input Setup
This feature applies to all models.
Setup
The power monitor calculates metering results based on scaled voltage and current inputs. Setting
up the analog inputs is necessary to obtain accurate, properly scaled metering results.
Related Functions
•
Wiring diagnostics
•
Configuration lock
Parameter
Description
Range
Default
User
Setting
Voltage mode
Should match the external electrical system and how it is
wired to the PowerMonitor voltage and current input
terminals. Refer to the wiring diagrams.
0 = Direct Delta
1 = Open Delta
2 = Wye
3 = Single Phase
4 = Demo, simulated results
5 = 1PT1CT-LL
6 = 1PT1CT-LN
0…4
2
PT primary
The primary value of the PT ratio (Pri:Sec) indicating the
nominal voltage present at the high-end of the transformer.
For direct connect, set the PT ratio to any valid 1:1 ratio (for
example, 480:480).
1.00… 50,000
480
PT secondary
The secondary value of the PT ratio (Pri:Sec) indicating the
nominal voltage present at the low-end of the transformer.
1…600
480
CT primary
The primary value of the CT ratio (Pri:5) indicating the nominal
current present at the high-end of the transformer. The
nominal CT rated current is 5 A.
5…50,000
5
System PF setting
Select range corresponding to expected power factor.
0 = Lead (-97…89)
1 = High (-85…98)
2 = Low (-52…-95)
2 = Low