Rockwell Automation 1408-EMxx PowerMonitor 1000 Unit User Manual
Page 98
98
Rockwell Automation Publication 1408-UM001D-EN-P - September 2013
Appendix A PowerMonitor 1000 Data Tables
Table 38 - Energy Log Results Parameters
CSP File No.
F26
CIP Instance
19
No. of Elements
21
No. of Words
42
Data Type
Float
Data Access
Read
Table 39 - Energy Log Results
Element
No.
Modbus
Address
Element Name
Range
TR1
TR2
EM1
EM2
EM3
Description
0
30701-2
Internal Record
Identifier.
•
•
•
1
30703-4
Timestamp Year of
record
-
•
•
•
The date and time when the
record was recorded.
2
30705-6
Timestamp Month/
Day
-
•
•
•
3
30707-8
Timestamp Hour/
Minute
-
•
•
•
4
30709-10
Timestamp Seconds/
Hundredths
-
•
•
•
5
30711-12
Status 1 Count xM
0…9,999,999
•
•
•
Status 1 Count times 1,000,000
6
30713-14
Status 1 Count x1
0…999,999
•
•
•
Status 1 count times 1
7
30715-16
Status 2 Count xM
0…9,999,999
•
•
•
Status 2 Count times 1,000,000
8
30717-18
Status 2 Count x1
0…999,999
•
•
•
Status 2 count times 1
9
30719-20
GWh Net
+/- 0…9,999,999
•
•
•
Net gigawatt hours
10
30721-22
kWatth Net
+/- 0.000…999,999
•
•
•
Net kilowatt hours
11
30723-24
GVARH Net
+/- 0…9,999,999
•
•
Net gigaVAR hours
12
30725-26
kVARh Net
+/- 0.000…999,999
•
•
Net kiloVAR hours
13
30727-28
GVAh Net
0…9,999,999
•
•
Net gigaVA hours
14
30729-30
kVAh Net
0.000…999,999
•
•
Net kiloVA hours
15
30731-32
kWatt Demand
+/- 0.000…9,999,999
•
•
The average real power during
the last demand period.
16
30733-34
kVAR Demand
+/- 0.000…9,999,999
•
•
The average reactive power
during the last demand period.
17
30735-36
kVA Demand
0.000…9,999,999
•
•
The average apparent power
during the last demand period.
18
30737-38
Demand PF
-100.0…+100.0
•
•
The average demand for PF during
the last demand period.
19
30739-40
Reserved
0
•
•
Reserved for future use.
20
30741-42
Reserved
0
•
•
Reserved for future use.