beautypg.com

Results, Commands, Related functions – Rockwell Automation 1408-EMxx PowerMonitor 1000 Unit User Manual

Page 34: Power metering

background image

34

Rockwell Automation Publication 1408-UM001D-EN-P - September 2013

Chapter 2 PowerMonitor 1000 Unit Features

Results

Demand metering results may be viewed using the following methods:

Web interface

LCD display

Communication

Demand results are not available via the HyperTerminal communication tool.

Commands

Controller command (EOI signal)

Related Functions

Status inputs

Time of use log

Configuration lock

Power Metering

This function applies to catalog numbers 1408-TR1 (power factor only), 1408-

TR2, and 1408-EM3.

Forced Demand

Sync Delay

(advanced setup)

If demand source 0 and demand period length 0 then this parameter determines how

long the unit waits for an EOI pulse, command, or broadcast after the expected control

pulse has not been received. If the EOI signal is not received before the waiting period

expires, a new demand period starts and a record is entered in the status log.
Special case: 0 = Wait forever

0…900 s

10

Demand

Broadcast

Master Select

(Ethernet setup)

0 = Slave, the unit uses its selected demand source to calculate demand. If demand

source = 3 (Ethernet demand broadcast) the unit will listen to the selected-broadcast

port number for a broadcast from the demand-sync master unit.
1 = Master, the unit broadcasts an EOI broadcast to the selected-UDP port number

when the selected demand source detects an EOI event.

0…1

0

Broadcast Port

Number

(Ethernet setup)

Specifies the listening or broadcast port for the UDP Ethernet-demand broadcast

message.

300…400

300

Parameter

Description

Range

Default

User

Setting

This manual is related to the following products: