Results, Commands, Related functions – Rockwell Automation 1408-EMxx PowerMonitor 1000 Unit User Manual
Page 34: Power metering
34
Rockwell Automation Publication 1408-UM001D-EN-P - September 2013
Chapter 2 PowerMonitor 1000 Unit Features
Results
Demand metering results may be viewed using the following methods:
•
Web interface
•
LCD display
•
Communication
Demand results are not available via the HyperTerminal communication tool.
Commands
•
Controller command (EOI signal)
Related Functions
•
Status inputs
•
Time of use log
•
Configuration lock
Power Metering
This function applies to catalog numbers 1408-TR1 (power factor only), 1408-
TR2, and 1408-EM3.
Forced Demand
Sync Delay
(advanced setup)
If demand source 0 and demand period length 0 then this parameter determines how
long the unit waits for an EOI pulse, command, or broadcast after the expected control
pulse has not been received. If the EOI signal is not received before the waiting period
expires, a new demand period starts and a record is entered in the status log.
Special case: 0 = Wait forever
0…900 s
10
Demand
Broadcast
Master Select
(Ethernet setup)
0 = Slave, the unit uses its selected demand source to calculate demand. If demand
source = 3 (Ethernet demand broadcast) the unit will listen to the selected-broadcast
port number for a broadcast from the demand-sync master unit.
1 = Master, the unit broadcasts an EOI broadcast to the selected-UDP port number
when the selected demand source detects an EOI event.
0…1
0
Broadcast Port
Number
(Ethernet setup)
Specifies the listening or broadcast port for the UDP Ethernet-demand broadcast
message.
300…400
300
Parameter
Description
Range
Default
User